..\Manuals\RCI-200-SER 

                                                                                                          Page 9 of 12 

PC or PLC Interfacing using MODBUS ASCII:

 

 
The RCI-200-SER can communicate directly to a PC or PLC using MODBUS ASCII protocol.  
Numerous off-the-shelf software packages have built-in MODBUS support.  The following information 
provides the MODBUS specific parameters necessary to configure the PC/PLC software. 
 

Message Format 
 

 
 
 

1)

 RCI-XXX-MDM = 2400 Baud 

 

ASCII Framing 

 

Start 

Address Function 

Data 

LRC 

End 

1 Char 

2 Chars  2 Chars  n Chars 2 Chars 2 Chars

CR,LF 

 
 

MODBUS Registers 

 
The functions and registers listed in the table below are the only ones implemented on all RCI products 
at this time. 
 

Description (Function) 

RCI-100-XXX 

RCI-200-XXX 

RCI-400-XXX 

RCI-800-XXX 

Read Relay Status (01) 

00001 

00001-00002 

00001-00004 

00001-00008 

Read Digital Input (02) 

10001 

10001-10002 

10001-10004 

10001-10008 

Read Analog Output (03) 

40001 

40001-40002 

40001-40004 

40001-40008 

Read Analog Input (04) 

30001 

30001-30002 

30001-30004 

30001-30008 

Set Relay Status (05) 

00001 

00001-00002 

00001-00004 

00001-00008 

Set Analog Output (06) 

40001 

40001-40002 

40001-40004 

40001-40008 

Set Multiple Relays (0F) 

00001 

00001-00002 

00001-00004 

00001-00008 

Set Multiple Analog Out (10) 

40001 

40001-40002 

40001-40004 

40001-40008 

 
 

Speed 

Start 

Data 

Parity 

Stop 

9600

1)

 1  7  E  1 

Содержание RCI-200 series

Страница 1: ...00 XXX If special or required 24 VDC 2 Dry Contacts and 2 Analog Inputs Input Remote Control Signal Interface XXX SER RS 232 485 Output 2 Form C Contacts and 2 Analog Outputs 117VAC 50 60Hz XXX RF9 90...

Страница 2: ...ducts or all non standard products may not be returned for restocking Pribusin Inc warrants equipment of its own manufacture to be free from defects in material and workmanship under normal conditions...

Страница 3: ...cks make for easy installation When connecting units on a PBX system make sure it can accept analog modem transmissions Serial systems connect via standard modem cable Standard Features Bi directional...

Страница 4: ...ter 232 485COM RS 232 RS 485 up to 128 devices RS 485 Bus R S 232 System A System B System C Additional Signal Booster s required for 32 devices see SPB 485 Manufactured By 11 25 9 25 4 5 www pribusin...

Страница 5: ......

Страница 6: ......

Страница 7: ......

Страница 8: ...0mA SLOBLO fuse It can be wired for 240VAC operation by removing de soldering power jumpers J1 J2 and installing soldering jumper J3 When changing the RCI 200 to 240VAC power make sure to change the f...

Страница 9: ...ts are connected to the RCI 200 in two fashions 1 Normal 3 wire connection or 2 two wire connection On a 3 wire connected input an external power supply or the 24V power output terminal of the RCI pro...

Страница 10: ...om the inputs Care must be taken when connecting the outputs to different devices so that no inadvertent ground loops are established Output Calibration Input Testing The outputs on the RCI 200 are fa...

Страница 11: ...nications failure occurs If H1 3 IN then analog output 1 will ramp to the setting of K1 and analog output 2 will ramp to the setting of K2 Both outputs will change at a rate determined by the setting...

Страница 12: ...ddress 1 2 3 etc so that the host may distinguish between them There may at most be as many remotes as there are inputs outputs on the host For example an RCI 200 system having two analog contact inpu...

Страница 13: ...perate as a host unit make sure that SW2 8 is flipped down Next set the number of remotes that the host is to communicate with using SW1 1 2 3 These switches are binary encoded as shown in the chart t...

Страница 14: ...e to convert the remote address to binary first SW1 1 SW1 2 SW1 3 Remote Address UP UP UP 1 DOWN UP UP 2 UP DOWN UP 3 DOWN DOWN UP 4 UP UP DOWN 5 DOWN UP DOWN 6 UP DOWN DOWN 7 DOWN DOWN DOWN 8 Next se...

Страница 15: ...2 Next set the number of channels on this remote using SW2 1 2 One channel is considered 1 analog input output plus 1 contact input output Hence an RCI 200 can have at most 1 channel SW2 1 SW2 2 Chann...

Страница 16: ...sters listed in the table below are the only ones implemented on all RCI products at this time Description Function RCI 100 XXX RCI 200 XXX RCI 400 XXX RCI 800 XXX Read Relay Status 01 00001 00001 000...

Страница 17: ...2 Number of Remotes 1 Address 1 Channels on Remotes 2 Example 3 An RCI 400 Host communicating with an RCI 400 Remote RCI 400 Host RCI 400 Remote Host Channels 4 Remote Channels 4 Number of Remotes 1 A...

Страница 18: ...ample 4 An RCI 800 Host communicating with 3 RCI 200 Remotes RCI 200 Host RCI 100 Remote 1 RCI 100 Remote 2 Host Channels 2 Number of Remotes 2 Channels on Remotes 1 Remote Channels 1 Address 1 Remote...

Страница 19: ...Page 12 of 12 RCI 800 Host Host Channels 8 Number of Remotes 3 Channels on Remotes 2 RCI 200 Remote 1 RCI 200 Remote 2 RCI 200 Remote 3 Remote Channels 2 Address 1 Remote Channels 2 Address 2 Remote...

Отзывы: