Operation
Page 30
The analog output is enabled only after selecting the range of output
retransmission from the RANGE mnemonic.
RANGE - selects the range of retransmission output as 20mA, 5V or 10V. The
relation between the engineering unit and electric signal generated in the terminals is
defined in the same way as shown for linear process scale configuration. Define two
points P1 (Eng Low, Lim Low) and P2 (Eng High, Lim High) as it is illustrated in
figure 20. Eng Low is the indication in the display in engineering units associated to
the electric signal Lim Low, and Eng High is the indication in display in engineering
units associated to the electric signal Lim High. Note that Lim Low and Lim High are
defined in percentage of output range and that the output signal saturates in these
points.
P1
P2
ENG LOW
ENG HIGH
LIM HIGH *
LIM LOW *
0
INDICATOR
OUTPUT
SIGNAL
DISPLAY VALUE
(*) % FULL-SCALE OUTPUT SIGNAL
Figure 20 - Analog output configuration
Level 5 - Calibration
Level 5 is described on section 4.5 on Calibration.
Level 6 - RS
Refer to the communication manual.