MA-5191A
21-10-2021
27 / 110
8.
COMMISSIONING
Before starting up the equipment, make sure that all connections are correct, respecting the
polarities indicated on the front of the unit.
The temperature sensor has the function of informing the charger of the ambient temperature
of the battery, in order to adjust the charging parameters accordingly. It should be installed
in the same room or cabinet as the battery, as close as possible to the battery. It does not
need to be in contact with the battery.
This equipment does not have an ignition switch, so it starts operating once the input voltage
is supplied to the terminals “1 Phase and 2 Neutral”.
If everything is correct, 5 seconds after connection, the green LED "Equipment in operation"
and the green LED "Charging status" will light up, fixed or blinking depending on the battery
charge status. All other LEDs should remain off in normal operation.
If this is not the case, see section “4.5 Signalling” to locate where the incident is. If this does
not solve the problem, see section "14 Diagnosis"
During the installation of the equipment, it must be verified that it is properly earthed. For this
purpose, it must be verified that the earth point of the charger is properly connected.
This equipment does not require an electrical protective earth because its plastic enclosure is
able to withstand electrical rigidity tests. For this reason, the equipment earth should not be
considered electrically safe.
The earthing of this equipment is functional and its connection is necessary to ensure that the
equipment complies with the specified conducted and radiated emission levels.