6
Packaged and Split Rooftop Ventilator
Installation - Packaged DX
Service Clearances
Unit
Size
A
L
W
J*
H
Unit
Weight
Outdoor
Air WH Qty
Pre-Wheel
Supply/
Exhaust
Filters*
Qty
Supply Final
Filters
(Pre-coil)**
Qty
Outdoor
Air
WH
Length Width Condensing
Section
Height
MP-1-1
22.1
98.6
52.5
30.1
59.3
2700
20x20x2
4
NA
20x20x2
4
MP-2-1
27.1
109
68.2
30.1
72.5
4500
25x25x2
4
16x25x2
8
MP-4-0
22
156
68
30
90
6400
20x25x2
6
16x20x2
12
MP-4-0^
22
156
68
30
90
6400
20x25x2
6
16x20x2
12
MPE-1-1
22.1
149.5
52.5
30.1
59.3
3400
20x20x2
4
20x25x2†
2†
20x20x2
4
MPE-2-1
27.1
163.2
68.2
30.1
72.5
5100
25x25x2
4
16x25x2‡
4‡
16x25x2
8
MPE-4-0
22
224
68
30
90
8300
20x25x2
6
16x20x2#
7#
16x20x2
12
MPE-4-0^
27
224
68
30
90
8300
25x25x2
6
20x20x2/
20x24x2
8
16x20x2
12
All dimensions are shown in inches. Weight shown in pounds. *Size and quantity is per airstream. **Dimension based upon
MERV 8 or 13 filters (MERV 14 filters are 4 in. thick).
†
Based upon a 30 / 36 in. energy wheel (16x25x2, quantity of 3 for 41 in.
energy wheel).
‡
Based upon a 52 in. energy wheel (16x16x2, quantity of 8 for 58 in. energy wheel).
#
Based upon a 52 / 58 in.
energy wheel (16x20x2, quantity of 8 for 74 in. energy wheel). ^Above 12,000 cfm. WH = weatherhood (aluminum mesh). Model
MPE includes energy wheel (not shown).
Unit Size
ACS
CC
End
OA
End
CS from
Unit
MP-1-1/MPE-1-1
40
42
42
18
MP-2-1/MPE-2-1
36
58
42
18
MP-4-0/MPE-4-0
36
52
58
18
All dimensions are shown in inches.
ACS = Access
CC = Control Center
OA = Outdoor Air Weatherhood
CS = condensing section
Typical Unit Weights and Dimensions
OA End
ACS
CS
CC End
CLEARANCE
CLEARANCE
Inlet/Discharge Locations
Unit Size
RA1
RA2
RA3
RA4
SB1
SB2
SB3
SB4
SS1
SS2
SS3
SS4
MP-1-1, MPE-1-1
41
5.8
5.6, 56.6 11.5
28
14
22
24
21
6.5
22
25
MP-2-1, MPE-2-1
56
6.1
5.9, 60.2
16
53
7.6
23.2
27
21
6.5
22.2
29
MP-4-0, MPE-4-0
48.8
9.6
9, 77
21.8
42
13
37.7
36
32
6.4
45.2
32
L
OUTDOOR AIR
WEATHERHOOD
SUPPLY AIR
DISCHARGE BOTTOM
RECIRC
DAMPER
OUTDOOR AIR
DAMPER
SUPPLY BLOWER
COMPRESSORS
A
CONTROL
CENTER
IG HEATER
H
SUPPLY FILTERS
W
J
SB1
SB2
SB4
SB3
RA3
RA4
RA2
RA1
SS1
SS2
SS3
SS4
RETURN AIR
INLET
DX COIL
SUPPLY AIR
DISCHARGE SIDE
© 2017 Mitsubishi Electric US, Inc.