Installation guide and Owner’s manual
Page 8/10
20201029
Pumping stations PSA-240/H
Item # 183036
6.2 PSA-240
Pumping station
The following table specifies the cable’s recommended length (L) of the On/Off
float for a maximum distance of 48 m (160') between the pumping station and
the treatment system. It presents different values for 1 and 2 Ecoflo biofilters
(or a dose of approximately 50 L and 100 L for other treatment systems).
Number
biofilter
(dose)
Pipe Ø
nominal
Length of the pipe between the pumping station and the treatment system
6 m (20')
12 m (40')
18 m (60')
24 m (80')
30 m (100')
36 m (120')
42 m (140')
48 m (160')
Length the On/Off float cable (presented by 'L' on the illustration above)
1
(50 L)
25 mm (1")
100 mm (4")
100 mm (4")
100 mm (4")
125 mm (5")
125 mm (5")
125 mm (5")
125 mm (5")
150 mm (6")
31 mm (1¼") 100 mm (4")
100 mm (4")
100 mm (4")
125 mm (5")
150 mm (6")
175 mm (7") 200 mm (8")** 200 mm (8")**
38 mm (1½") 100 mm
(4")*
100
mm (4")*
125 mm (5")
150 mm (6")
175 mm (7")
200 mm (8")** 225 mm (9")** 250 mm (10")**
50 mm (2")
100 mm (4")
125 mm (5")
175 mm (7") 225 mm (9")**
na
na
na
na
2
(100 L)
25 mm (1")
175 mm (7")
175 mm (7") 200 mm (8")** 200 mm (8")** 200 mm (8")** 225 mm (9")** 225 mm (9")** 250 mm (10")**
31 mm (1¼") 175 mm (7") 200 mm (8")** 200 mm (8")** 225 mm (9")** 250 mm 10")** 250 mm (10")**
na
na
38 mm (1½") 175 mm (7") 200 mm (8")** 225 mm (9")** 250 mm (10")**
na
na
na
na
50 mm (2") 200 mm (8")** 250 mm (10")**
na
na
na
na
na
na
*The length of the cable is pre-set to that length at the plant.
**The alarm float has to be moved 50 mm higher than its initial position on the float tree. The length of the cable must remain at 3" (75 mm).
Finally, adjust the valve so that water flows into the Ecoflo
biofilter at an acceptable rate and the dosage time for each hydraulic event
(40 L, 8.8 imp. gallons, 10 US gallons) is at least 30 seconds. To check if the dosage is appropriate, the tipping bucket should fill-up a
maximum of 12 times per hydraulic event.
6.4 PSA-240H
Pumping station
The following table specifies the required distance between the On/Off floats (H) according to the dosage required for the treatment
system.
Required dose
Distance between floats (H)
Length of the On/Off float cable
(L)
50 L
17 cm
L is pre-set at 100 mm (4") at the plant
100 L
34 cm
150 L
51 cm
200 L
69 cm
250 L
86 cm
7. Maintenance
The pumping station has mechanical components, therefore, it is preferable to conduct an annual preventive inspection. Furthermore,
it is important to comply with the regulations regarding the septic tank emptying in order to prevent large particles from escaping the
septic tank and blocking the pump. We strongly recommend you empty your pumping station at the same time as your septic tank.
On/Off float
**See note
Alarm
float
75 mm (3")