Installation guide and Owner’s manual

 

Page 6/10

 

20201029 

Pumping stations PSA-240/H 

 

Item # 183036 

To wire the system, two (2) in-ground double strand supply cables are required. It is preferable to protect the wires with the 
appropriate piping before burying them. To pass wires through the pumping station’s wall, use watertight bulkhead union fittings. 

 

 

 

Note: Two independant circuit-breakers must be used to connect the pump and the alarm box. Each circuit must have an 
independent breaker of sufficient intensity equipped with a ground wire protection. 

 

 

Important: before the pumping station start-up, check if the float holding device for the transportation has been removed. Also 
check if the floats are ready and in the proper position for operation. 

STEP 5 – Final backfill 

 

Close the lid so nothing falls into the pumping station during backfill. 

 

Isolate the pipes if required. 

 

Backfill the pumping station and the pipes with material void of any organic 
matter, impervious soil, stones, debris, particles larger the 20 mm (¾") in 
diameter or any other object that could damage the pumping station.  

 

The backfill material must be placed with care and not dumped (do not 
compact with bulldozer).  

 

Allow space for ground cover and make sure the lids are at least 50 mm (2") above the surface of the landscaped lot. 

 

Finalise the backfill with a layer of soil that encourages vegetation growth. 

STEP 6 - Alarm box installation 

The pumping station is equipped with a high-water-level float connected to an alarm system. This alarm 
system must be installed inside the residence (home) so it can be heard when it is activated. The following 
information describes how the system works. 
 
A red indicator lights up when the water level in the Ecoflo biofilter is unusually high. If an alarm is 
activated, contact Premier Tech's After-Sales Service Department because the incident has to be 
checked. To silence the alarm, press the “SILENCE” button.  
 
The “TEST” button lets you check if the alarm system is working properly. During a test, the red indicator 
should light up and an audio alarm should be heard. 
 
In the event of a power failure, the alarm system continues to function on an emergency 9-volt alkaline battery (not supplied). Using a 
rechargeable battery is not recommended.  
 
NOTE: Replace the emergency battery every 12 months, each time the alarm is activated or whenever there is a power failure. If 
the battery is weak, the system will beep once every minute. When this occurs, replace the battery immediately.  
 

 

 

PSA-240 and PSA-240L 

Wiring diagram 

Wrap black electrical tape 
around the white wire of the 
On/Off float 

White 

Alarm box wire 

Alarm 

float 

Pump 

On/Off 
float 

120 VAC power 
cable 

Black 

White 

Black

 

White 

Green - ground 

Ground 

Green - ground 

White

 

Black

 –

 L

Black

 

PSA-240H 

Wiring diagram 

Double 

Alarm box wire 

Alarm 

float 

Pump 

Double 
On/Off 
float 

120 VAC  
power cable 

Black 

Black 

White 

White 

Green - ground 

Green - ground 

Ground 

Red 

Black

 –

 L

Black

  

White

 

PSR-060 or PSR-140 
riser (if required) 

Maximum 91 cm (36") 

Alarm box for pumping 

station 

Содержание REWATEC PSA-240

Страница 1: ...OWNER S MANUAL AND INSTALLATION GUIDE Pumping stations 2020 Made in Canada...

Страница 2: ...ng station is normally used to feed low pressure distribution systems for sand filters and seepage beds when a dosing volume between 150 and 255 L is required Models PSA 240 PSA 240H Material reservoi...

Страница 3: ...coupling for water outlet pipe 50 mm 2 nominal Flexible coupling for water inlet pipe 100 mm 4 nominal 2 Dimensions description and location 2 1 Dimensions PLAN VIEW PSA 240 L H pumping station base B...

Страница 4: ...SA 240 and PSA 240H 2 3 Component location The PSA 240 and PSA 240H pumping stations must always be installed after the septic tank or after the effluent filter container if such is the case They shou...

Страница 5: ...t damaged during transportation Ensure rapid growth of vegetation to prevent soil erosion The pumping station must be accessible at all times do not cover the lid The lid must be at least 50 mm 2 abov...

Страница 6: ...lluent penetrates the biofilter Refer to the illustration PSA 240 pumping station before an Ecoflo biofilter in section 2 3 If the distance between the pumping station and the biofilter is greater tha...

Страница 7: ...n The pumping station is equipped with a high water level float connected to an alarm system This alarm system must be installed inside the residence home so it can be heard when it is activated The f...

Страница 8: ...astener that ties it to the reservoir do not leave the fastener in the pumping station and perform a visual inspection Then place the pump in the reservoir and connect the water outlet pipe using the...

Страница 9: ...m 9 250 mm 10 na na na na 50 mm 2 200 mm 8 250 mm 10 na na na na na na The length of the cable is pre set to that length at the plant The alarm float has to be moved 50 mm higher than its initial posi...

Страница 10: ...tank installer or septic tank pumper can generally take care of the situation 8 5 Odours The position of the air vent as well as other factors unrelated to the pumping station itself can prevent septi...

Страница 11: ...to access to the Pumping Station including without limiting the generality of the foregoing excavation snow removal or demolition 5 PARTICULAR EXCLUSIONS It is further expressly understood that the Cu...

Отзывы: