PD6700-0L1 Field-Mount Loop-Powered Process Meter
Instruction Manual
20
Factory Defaults & User
Settings
The following table shows the factory setting for most
of the programmable parameters on the meter. Next
to the factory setting, the user may record the new
setting for the particular application.
Model: _____________________________________
S/N: _______________________________________
Date: ______________________________________
Parameter
Display
Default
Setting
User
Setting
Basic Setup
Level
Decimal Point
DECIMAL
1111.1
Input 1
INPUT 1
4.000 mA
Display 1
DSPLY 1
0.0
Input 2
INPUT 2
20.00 mA
Display 2
DSPLY 2
100.0
Tank Indicator
0%
0 PCT
0.0
Tank Indicator
100%
100 PCT
100.0
Lower Display
BOTTOM
Tag
Bargraph
GRAPH
On
Tag
TAG
TANK 1
Advanced Features
Output
OUTPUT
Off
Filter
FILTER
Low
Volume
Decimal Point
vOl
DECIMAL
0000000
Volume Scale
Number of
Points
NO PTS
02
Volume Scale
Input 1
INPUT 1
0.0
Volume
Display 1
DSPLY 1
0
Volume
Scale Input 2
INPUT 2
100.0
Volume
Display 2
DSPLY 2
100,000
Multipoint
MULTIPT
Disable
Password
Password
PASSWRD
00000
(unlocked)
Troubleshooting
Due to the many features and functions of the meter,
it’s possible that the setup of the meter does not
agree with what an operator expects to see. If the
meter is not working as expected, refer to the
Diagnostics
menu and consult the recommendations
described in the following table.
Troubleshooting Tips
Symptom
Check/Action
No display or faint
display
Check input signal
connections.
Perform hard reset by shorting
S+ and S- terminals.
Level display
unsteady
Increase filter setting in
Advanced
menu.
Meter displays error
message during
calibration
(
SPN ERR
)
Check signal connections.
Verify minimum input span
requirements.
Level display flashes
99999 or -9999
Check input signal and scaling
within range of 99999 & -9999
Volume display
flashes
9999999 or -999999
Check level display within
volume scale range of
9999999 & -999999.
Display response is
too slow
Check filter setting to see if it
can be lowered to
LO
or
OFF
.
If the display locks
up or the meter does
not respond at all
Perform hard reset by shorting
S+ and S- terminals.
Backlight does not
appear.
Backlight may not be
noticeable under good lighting
conditions.
Check connections are as
shown in
Figure 5
or
Figure 6
on page
8
.
SafeTouch buttons
do not respond
Mechanical button was
pushed or SafeTouch slide
switch is in lock position. The
SafeTouch buttons will be re-
enabled automatically 60
seconds
after the last button
push.
If slide switch on connector
board is in Lock position,
switch to Unlock.
Sunlight can interfere with the
sensors. It is recommended to
shield the window from
sunlight while operating the
buttons by standing so as to
block direct sunlight.
Other symptoms not
described above
Call Technical Support for
assistance.