PD663 Explosion-Proof Loop-Powered Meter
Instruction Manual
8
Setup and Programming
There is
no need to recalibrate
the meter for
milliamps when first received from the factory.
The meter is
factory calibrated
for milliamps prior
to shipment. The calibration equipment is traceable
to NIST standards.
Overview
There are no jumpers involved in the setup process of
the meter.
Setup and programming is done through the front
panel buttons.
After all connections have been completed and
verified, apply power to the loop.
For
Quick User Interface Reference
go to page
Buttons and Display
Button/
Symbol
Description
MENU
Menu button to enter programming
mode. Press and hold for 5 seconds
to access the
Advanced
features of
the meter.
ENTER
Enter button to access a menu or
accept a setting.
RESET
Right arrow to scroll through the
menus or move to the next digit or
decimal position during
programming.
Resets the Max or Min display value
when pressed while showing Max or
Min value.
MAX
Up arrow to scroll through the
menus, decimal point, or to
increment the value of a digit.
Displays the Max then Min display
values when pressed during normal
run mode.
Setting Numeric Values
The numeric values are set using the
Right
and
Up
arrow buttons. Press the
Right
arrow to select next
digit and the
Up
arrow to increment digit. The two left-
most digits on the display are set as a single digit,
able to display -19 to 29.
The digit being changed blinks.
Press the
Enter
button, at any time, to accept a
setting or
Menu
button to exit without saving changes.
The decimal point is set using the
Right
or
Up
arrow
button in the
Setup-decimal point
menu.
Programming the Meter
The meter may either be scaled (
SCL
) without
applying an input or calibrated (
Cal
) by applying an
input. The meter comes factory calibrated to NIST
standards, so for initial setup, it is recommended to
use the (
SCL
) function. The Program menu contains
the Scale (
SCL
) and the Calibrate (
Cal
) menus.
Process inputs may be scaled or calibrated to any
display within the range of the meter.
Additional parameters, not needed for most
applications, are viewed and programmed with the
Main Menu
The main menu consists of the most commonly used
functions:
Decimal Point Location
,
Scale
, and
Calibration
.
Press
Menu
button to enter Programming Mode then
press the
Up
Arrow
button to scroll through the main
menu.
Press
Menu
, at any time, to exit and return to Run
Mode. Changes made to settings prior to pressing
Enter
are not saved.
Changes to the settings are saved to memory only
after pressing
Enter
.
The display moves to the next menu every time a
setting is accepted by pressing
Enter
.