PD154 & PD158 Vigilante II Annunciators 

Instruction Manual 

 

8

 

 

Compliance Information 

Safety 

UL Listed 

USA and Canada 

UL 508 Industrial Control Equipment 

UL File Number 

E160849 

Front Panel 

UL Type 4X, NEMA 4X, IP65; panel 

gasket provided 

Low Voltage  

Directive 

EN 61010-1:2010 

Safety requirements for measurement, 

control, and laboratory use 

 

Electromagnetic Compatibility 

Emissions 

EN 55022:2010 

Class A ITE emissions requirements 

Radiated 

Emissions 

Class A 

AC Mains  

Conducted  

Emissions  

Class A 

Immunity

 

EN 61326-1:2013 

Measurement, control, and labora-

tory equipment 

EN 61000-6-2:2005 

EMC heavy industrial generic 

immunity standard 

RFI - Amplitude 

Modulated 

80 -1000 MHz 10 V/m 80% AM 

(1 kHz) 

1.4 - 2.0 GHz 3 V/m 80% AM (1 kHz) 

2.0 - 2.7 GHz 1 V/m 80% AM (1 kHz) 

Electrical Fast 

Transients 

±2kV AC mains, ±1kV other 

Electrostatic  

Discharge 

±4kV contact, ±8kV air 

RFI - Conducted  10V, 0.15-80 MHz, 1kHz 80% AM 

AC Surge 

±2kV Common, ±1kV Differential 

Surge 

1KV (CM) 

Power-

Frequency  

Magnetic Field 

30 A/m 70%V for 0.5 period 

Voltage Dips 

40%V for 5 & 50 periods 

70%V for 25 periods 

Voltage  

Interruptions 

<5%V for 250 periods 

 

Safety Information 

 

 

  Read complete instructions prior to installation 

and operation of the instrument. 

 

  Risk of electric shock. 

  Hazardous voltages exist within enclosure. 

Installation and service should be performed only 

by trained service personnel. 

 

Installation 

There is no need to remove the instrument from its 

case to complete the installation, wiring, and setup. 

Unpacking 

Remove the instrument from box. Inspect the 

packaging and contents for damage. Report 

damages, if any, to the carrier. 
If any part is missing or the unit malfunctions, please 

contact your supplier or the factory for assistance. 

Panel Mounting 

  Prepare a standard 1/8 DIN vertical panel cutout 

– 1.772" x 3.622" (45 mm x 92 mm). Refer to  

Figure 2

 for more details. 

  Clearance: allow at least 4" (102 mm) behind the 

panel for wiring. 

  Panel thickness: 0.04" - 0.25" (1.0 mm - 6.4 mm).  

Recommended minimum panel thickness to 

maintain Type 4X rating: 0.06" (1.5 mm) steel 

panel, 0.16" (4.1 mm) plastic panel. 

  Remove the two mounting brackets provided with 

the annunciator (back-off the two screws so that 

there is ¼" (6.4 mm) or less through the bracket. 

Slide the bracket toward the front of the case and 

remove). 

  Insert the unit into the panel cutout. 

  Install mounting brackets and tighten the screws 

against the panel. To achieve a proper seal, 

tighten the mounting bracket screws evenly until 

the front is snug to the panel along its short side. 

DO NOT OVER TIGHTEN, as the rear of the 

panel may be damaged. 

 

 

Figure 2. Panel Cutout and Mounting 

 

 

Panel

Gasket

Mounting

Bracket

Mounting

Screw

Removable

Connectors

1.772"

(45mm)

Panel Cutout

to DIN 43700

Square Corners

to 0.060"

(1.5mm)

Max Radius

B

Tolerances:

A: +0.032 (+0.8mm)

     -0.000 (-0.0mm)

B: +0.024 (+0.6mm)

     -0.000 (-0.0mm)

3.622"

(92mm)

A

Top View

Front View

Содержание PD154-6R2-1

Страница 1: ...Functions Sunlight Readable Indication Shallow Depth Case Extends Only 3 6 91 mm Behind Panel Isolated 24 VDC 200 mA Transmitter Power Supply AC Models 2 SPDT Relays for Alarm Activated Devices Opera...

Страница 2: ...y Information and Terms Conditions on www predig com for complete details 2020 Precision Digital Corporation All rights reserved Introduction The Vigilante II is a multipurpose panel mounted alarm ann...

Страница 3: ...AC Enclosures Model of Units Description Mounting PDA2301 V 1 Plastic NEMA 4X Enclosure Through Door PDA2302 V 2 Plastic NEMA 4X Enclosure Through Door PDA2303 V 3 Plastic NEMA 4X Enclosure Through Do...

Страница 4: ...Input Types 11 External Pushbutton Connections 11 Multiple Unit First Out Indication Connections 11 Setup and Programming 12 Overview 12 Front Panel Pushbuttons and Status LED Indicators 12 Full Func...

Страница 5: ...sions Side View 9 Figure 4 Case Dimensions Top View 9 Figure 5 Connector Labeling for PD154 6R2 1 9 Figure 6 Connector Labeling for PD158 6R2 1 9 Figure 7 Connector Labeling for PD154 7R2 0 9 Figure 8...

Страница 6: ...steps 4 and 5 for all input channels Press and hold ACK for five seconds to return to normal operation with the programmed input types Basic Connections All connections are made to removable screw ter...

Страница 7: ...orage temperature range 40 to 85 C Relative humidity 0 to 90 non condensing Connections Removable screw terminal blocks for 12 to 22 AWG wire Enclosure 1 8 DIN high impact plastic UL 94V 0 front color...

Страница 8: ...only by trained service personnel Installation There is no need to remove the instrument from its case to complete the installation wiring and setup Unpacking Remove the instrument from box Inspect th...

Страница 9: ...0 C or 60 75 C insulation for all line voltage connections Observe all safety regulations Electrical wiring should be performed in accordance with all applicable national state and local codes to prev...

Страница 10: ...eparate in put channel and all emitters connected to common All channels are factory set for transistor inputs normally in the cutoff or off state For normally active saturation state or on transistor...

Страница 11: ...nputs OC or TTL signals However throughout this manual the term pushbutton is used to describe these external inputs Please refer to the chart below for signal logic External Input Type Active When Sw...

Страница 12: ...ISA sequences A F1A and F2A which reset acknowledged channels automatically See selected sequence details for complete function description see Full Sequence Descriptions page 17 LED TEST SILENCE ACK...

Страница 13: ...ition Alarm Conditions for normally closed inputs 1 An open contact between an input channel and common will cause an alarm condition 2 An off or cutoff state transistor between an input channel and c...

Страница 14: ...cleared Relay Fail Safe In fail safe operation a relay coil is energized in non alarm condition In case of power failure relays will go to alarm state Fail safe operation is set independently for eac...

Страница 15: ...ton enable disable option see page 15 and no lock in option see page 16 Relay Operation Overview The following figure illustrates the operation of the relays ACK Pressed ON OFF Relay 1 ON OFF Relay 2...

Страница 16: ...conds to return to operation The green power LED will blink quickly to indicate the unit is in the advanced programming mode The unit will automatically leave setup mode if no pushbutton is pressed fo...

Страница 17: ...The input is in alarm state and the channel has not been acknowledged with the ACK pushbutton Acknowledge The alarm state is acknowledged with the ACK pushbutton This will restart the first out indica...

Страница 18: ...dge Steady Steady Off Normal Off Off Off Condition LED Horn 1st Pt Next Pt Normal Off Off Off Alert Flash Steady On Normal Flash Off On ACK Pushbutton Acknowledge Off Off Off Condition LED Horn 1st Pt...

Страница 19: ...al Off Off Off Alert Intermittent Flash Fast Flash On RESET Pushbutton 1st Out Reset Fast Flash Fast Flash On ACK Pushbutton Acknowledge Steady Steady Off Normal Off Off Off Maintained Alarm ACK befor...

Страница 20: ...Flow Chart Condition LED Horn Normal Off Off Alert Steady On Normal Off Off Condition LED Horn Normal Off Off Alert Flash On Normal Flash On ACK Pushbutton Acknowledge Steady Off RESET Pushbutton Rese...

Страница 21: ...ledge Steady Steady Off RESET Pushbutton Reset Off Off Off Condition LED Horn 1st Pt Next Pt Normal Off Off Off Alert Flash Steady On ACK Pushbutton Acknowledge Steady Steady Off Normal Steady Steady...

Страница 22: ...echnical standards and when applicable or required a European Union notified body certification Standards EN 55022 2003 EN 61000 6 2 2001 EN 61010 1 2001 EN 61326 2006 The standards EN 55022 2003 EN 6...

Страница 23: ...PD154 PD158 Vigilante II Annunciators Instruction Manual 23 This page left blank intentionally...

Страница 24: ...www predig com LIM158_F SFT043 Ver 1 0 up 05 20 Contact Precision Digital Technical Support Call 800 610 5239 or 508 655 7300 Fax 508 655 8990 Email support predig com Sales Support Call 800 343 1001...

Отзывы: