PD154 & PD158 Vigilante II Annunciators 

Instruction Manual 

 

16

 

 

Silence Pushbutton 

Enable/Disable 

1.  Press and hold 

ACK

 and 

RESET

 for 3 

seconds until all LEDs cycle, then release. 

2.  Press 

RESET

 within 3 seconds of release 

while LEDs cycle.

1

 

3.  Press 

RESET

 within 3 seconds of release 

while LEDs blink.

1

 

4.  Press the 

ACK

 pushbutton twice until LED 3 

is either off or brightly on. 

5.  Press the 

RESET

 pushbutton to turn LED 3 

off to disable the silence pushbutton or 

brightly on to enable the silence pushbutton. 

6.  Press 

ACK

 to accept the silence pushbutton 

setting. 

7.  Press and hold 

ACK 

for five seconds to 

return to normal operation. 

The green power LED will blink quickly to indicate the 

unit is in the advanced programming mode. The unit 

will automatically leave setup mode if no pushbutton 

is pressed for 3 minutes. 

Note:

 LED 1 and 2 are used for relay fail-safe setup 

(see page 14)

 

 

1

The unit will automatically leave setup mode if steps 

2 and 3 are not followed. 

No Lock-In Sequence Option 

ISA sequence option 4 

no lock-in

, may be added to 

any sequence. Momentary alarms will clear without 

the 

ACK

 pushbutton. Sequences A, F1A, F2A, and 

F3A will automatically clear any momentary alarm. 

Sequences M, F1M, and F2M will clear all momentary 

alarms when the 

RESET

 pushbutton is used, 

regardless of what channels have previously been 

acknowledged with 

ACK

Selecting No Lock-In Operation 

1.  Press and hold 

ACK

 and 

RESET

 for 3 

seconds until all LEDs cycle, then release. 

2.  Press 

RESET

 within 3 seconds of release 

while LEDs cycle.

1

 

3.  Press 

RESET

 within 3 seconds while LEDs 

blink.

1

 

4.  Press the 

ACK

 pushbutton three times until 

LED 4 is either off or brightly on. 

5.  Press the 

RESET

 pushbutton to turn LED 4 

off to disable the 

no lock-in option or on to enable the no lock-

in option. 

6.  Press 

ACK

 to accept the option setting. 

7.  Press and hold 

ACK 

for five seconds to 

return to operation. 

The green power LED will blink quickly to indicate the 

unit is in the advanced programming mode. The unit 

will automatically leave setup mode if no pushbutton 

is pressed for 3 minutes. 

Note:

 LED 1 and 2 are used for relay fail-safe setup 

(see page 14), and LED 3 is used for silence 

pushbutton enable/disable (see page 15). 

1

The unit will automatically leave setup mode if steps 

2 and 3 are not followed. 

Reset to Factory Defaults 

1.  Hold the 

ACK

 and 

RESET

 pushbuttons for 3 sec-

onds until all red LEDs cycle. Release once the 

LEDs begin to cycle. 

2.  Press and hold the 

RESET

 button for 5 seconds. If 

the 

RESET

 button is not pressed within 3 seconds 

of releasing 

ACK

 and 

RESET

, the unit will return 

to run mode without reset. 

3.  Reset the 4-position switch on the rear of the con-

trol to the indicated default settings. 

 

Factory 

Default 

Switch 

Positions 

 

 

 

Troubleshooting 

If the annunciator is not working as expected, refer to 

the recommendations below. 

Troubleshooting Tips 

Symptom 

Check/Action 

Power LED off 

Check power at power 

connector 

Audible alarm does not 

sound when alarm state 

detected 

Check: 

1.  Rear switch position 4  

is ON. 

2.  No external pushbutton 

contacts on the input 

connector are shorted. 

Power light blinks and 

channel/point indicators 

flash intermittently when 

powered up. 

Check that no external 

pushbutton contacts on the 

signal connector are shorted  

to common. 

Display sequence does not 

function as expected. 

Check: 

1.  Verify sequence selection 

as shown on page 

13

2.  Check that no external 

pushbutton contacts on the 

input connector are 

shorted.  

If the display locks up or 

the unit does not respond 

at all  

Cycle the power to restart the  

microprocessor. 

Relay operation is 

reversed 

Check: 

1.  Fail-safe settings as shown 

on page 

14

2.  Wiring of relay contacts 

Other symptoms not 

described above 

Call Technical Support for  

assistance. 

 

To reset unit to factory default settings of sequence 

F2A-1, first out indication with silence and 

acknowledge pushbuttons with automatic reset,  

see 

Reset to Factory Defaults

.

Содержание PD154-6R2-1

Страница 1: ...Functions Sunlight Readable Indication Shallow Depth Case Extends Only 3 6 91 mm Behind Panel Isolated 24 VDC 200 mA Transmitter Power Supply AC Models 2 SPDT Relays for Alarm Activated Devices Opera...

Страница 2: ...y Information and Terms Conditions on www predig com for complete details 2020 Precision Digital Corporation All rights reserved Introduction The Vigilante II is a multipurpose panel mounted alarm ann...

Страница 3: ...AC Enclosures Model of Units Description Mounting PDA2301 V 1 Plastic NEMA 4X Enclosure Through Door PDA2302 V 2 Plastic NEMA 4X Enclosure Through Door PDA2303 V 3 Plastic NEMA 4X Enclosure Through Do...

Страница 4: ...Input Types 11 External Pushbutton Connections 11 Multiple Unit First Out Indication Connections 11 Setup and Programming 12 Overview 12 Front Panel Pushbuttons and Status LED Indicators 12 Full Func...

Страница 5: ...sions Side View 9 Figure 4 Case Dimensions Top View 9 Figure 5 Connector Labeling for PD154 6R2 1 9 Figure 6 Connector Labeling for PD158 6R2 1 9 Figure 7 Connector Labeling for PD154 7R2 0 9 Figure 8...

Страница 6: ...steps 4 and 5 for all input channels Press and hold ACK for five seconds to return to normal operation with the programmed input types Basic Connections All connections are made to removable screw ter...

Страница 7: ...orage temperature range 40 to 85 C Relative humidity 0 to 90 non condensing Connections Removable screw terminal blocks for 12 to 22 AWG wire Enclosure 1 8 DIN high impact plastic UL 94V 0 front color...

Страница 8: ...only by trained service personnel Installation There is no need to remove the instrument from its case to complete the installation wiring and setup Unpacking Remove the instrument from box Inspect th...

Страница 9: ...0 C or 60 75 C insulation for all line voltage connections Observe all safety regulations Electrical wiring should be performed in accordance with all applicable national state and local codes to prev...

Страница 10: ...eparate in put channel and all emitters connected to common All channels are factory set for transistor inputs normally in the cutoff or off state For normally active saturation state or on transistor...

Страница 11: ...nputs OC or TTL signals However throughout this manual the term pushbutton is used to describe these external inputs Please refer to the chart below for signal logic External Input Type Active When Sw...

Страница 12: ...ISA sequences A F1A and F2A which reset acknowledged channels automatically See selected sequence details for complete function description see Full Sequence Descriptions page 17 LED TEST SILENCE ACK...

Страница 13: ...ition Alarm Conditions for normally closed inputs 1 An open contact between an input channel and common will cause an alarm condition 2 An off or cutoff state transistor between an input channel and c...

Страница 14: ...cleared Relay Fail Safe In fail safe operation a relay coil is energized in non alarm condition In case of power failure relays will go to alarm state Fail safe operation is set independently for eac...

Страница 15: ...ton enable disable option see page 15 and no lock in option see page 16 Relay Operation Overview The following figure illustrates the operation of the relays ACK Pressed ON OFF Relay 1 ON OFF Relay 2...

Страница 16: ...conds to return to operation The green power LED will blink quickly to indicate the unit is in the advanced programming mode The unit will automatically leave setup mode if no pushbutton is pressed fo...

Страница 17: ...The input is in alarm state and the channel has not been acknowledged with the ACK pushbutton Acknowledge The alarm state is acknowledged with the ACK pushbutton This will restart the first out indica...

Страница 18: ...dge Steady Steady Off Normal Off Off Off Condition LED Horn 1st Pt Next Pt Normal Off Off Off Alert Flash Steady On Normal Flash Off On ACK Pushbutton Acknowledge Off Off Off Condition LED Horn 1st Pt...

Страница 19: ...al Off Off Off Alert Intermittent Flash Fast Flash On RESET Pushbutton 1st Out Reset Fast Flash Fast Flash On ACK Pushbutton Acknowledge Steady Steady Off Normal Off Off Off Maintained Alarm ACK befor...

Страница 20: ...Flow Chart Condition LED Horn Normal Off Off Alert Steady On Normal Off Off Condition LED Horn Normal Off Off Alert Flash On Normal Flash On ACK Pushbutton Acknowledge Steady Off RESET Pushbutton Rese...

Страница 21: ...ledge Steady Steady Off RESET Pushbutton Reset Off Off Off Condition LED Horn 1st Pt Next Pt Normal Off Off Off Alert Flash Steady On ACK Pushbutton Acknowledge Steady Steady Off Normal Steady Steady...

Страница 22: ...echnical standards and when applicable or required a European Union notified body certification Standards EN 55022 2003 EN 61000 6 2 2001 EN 61010 1 2001 EN 61326 2006 The standards EN 55022 2003 EN 6...

Страница 23: ...PD154 PD158 Vigilante II Annunciators Instruction Manual 23 This page left blank intentionally...

Страница 24: ...www predig com LIM158_F SFT043 Ver 1 0 up 05 20 Contact Precision Digital Technical Support Call 800 610 5239 or 508 655 7300 Fax 508 655 8990 Email support predig com Sales Support Call 800 343 1001...

Отзывы: