PD154 & PD158 Vigilante II Annunciators 

Instruction Manual 

 

15 

 

Relay Fail-Safe Programming Example 

The following is an example of relay fail-safe setup. 

Relays 1 and 2 are changed from the default settings 

of normal operation to fail-safe operation.

 

1.  Press and hold 

ACK

 and 

RESET

 for 3 sec-

onds. When all LEDs cycle, release. 

2.  Press 

RESET

 within 3 seconds of release 

while LEDs cycle. All LEDs blink in unison. 

3.  Press 

RESET

 again within 3 seconds while 

LEDs blink 

 

4.  LED 1 will be off 

indicating normal 

operation of relay 1. 

LEDs 2 through 4 

will be dim. 

 

 

5.  Press Reset to 

change LED 1 from 

off to on, setting 

relay 1 for fail-safe 

operation. 

 

 

6.  Press 

ACK

 to 

confirm the setting 

for relay 1and 

proceed to program 

relay 2. 

 

7.  Press 

RESET

 to 

change LED 2 from 

off to on, setting 

relay 2 for fail-safe 

operation. 

 

 

8.  Press 

ACK

 to confirm the setting for relay 2. 

9.  Press and hold 

ACK

 for 5 seconds to return 

to normal operation. 

 

Note:

 LEDs 3 and 4 are used for the silence 

pushbutton enable/disable option (see page 15)  

and no lock-in option (see page 16) 
 

Relay Operation Overview 

The following figure illustrates the operation of the 

relays. 

ACK

Pressed

ON

OFF

Relay 1

ON

OFF

Relay 2

ON

OFF

Relay 1

ON

OFF

Relay 2

N

O

R

M

A

L

FA

IL

-S

A

FE

Alarms

Cleared

Alarm

Occurance

 

Relay On:

 Relay is energized 

Relay Off:

 Relay is de-energized. 

Alarm Occurrence:

 A new alarm occurs when there 

is no previous unacknowledged alarm. 

ACK Pressed:

 The Acknowledge pushbutton is 

pressed, acknowledging the alarm. 

Alarms Cleared:

 All LED indicators are cleared of 

alarm state indication 

 

Audible Horn Enable/Disable 

The annunciator contains an audible internal horn. 

This horn may be disabled with the rear-mounted 

switch located above the signal connector. To enable 

the horn, move switch 4 to the ON position. To 

disable the horn, move switch 4 to the OFF position. 
 

 

Sequence 

F2A 

Horn 

Enabled 

 

 

Sequence 

F2A 

Horn 

Disabled 

 

 

Enabling/Disabling Silence 

Option 

ISA sequence option 1, 

Silence Pushbutton

, includes 

a silence pushbutton. This option may be disabled, 

removing any effects of the silence pushbutton or 

silence pushbutton external contact. This option is 

enabled by factory default. 

Содержание PD154-6R2-1

Страница 1: ...Functions Sunlight Readable Indication Shallow Depth Case Extends Only 3 6 91 mm Behind Panel Isolated 24 VDC 200 mA Transmitter Power Supply AC Models 2 SPDT Relays for Alarm Activated Devices Opera...

Страница 2: ...y Information and Terms Conditions on www predig com for complete details 2020 Precision Digital Corporation All rights reserved Introduction The Vigilante II is a multipurpose panel mounted alarm ann...

Страница 3: ...AC Enclosures Model of Units Description Mounting PDA2301 V 1 Plastic NEMA 4X Enclosure Through Door PDA2302 V 2 Plastic NEMA 4X Enclosure Through Door PDA2303 V 3 Plastic NEMA 4X Enclosure Through Do...

Страница 4: ...Input Types 11 External Pushbutton Connections 11 Multiple Unit First Out Indication Connections 11 Setup and Programming 12 Overview 12 Front Panel Pushbuttons and Status LED Indicators 12 Full Func...

Страница 5: ...sions Side View 9 Figure 4 Case Dimensions Top View 9 Figure 5 Connector Labeling for PD154 6R2 1 9 Figure 6 Connector Labeling for PD158 6R2 1 9 Figure 7 Connector Labeling for PD154 7R2 0 9 Figure 8...

Страница 6: ...steps 4 and 5 for all input channels Press and hold ACK for five seconds to return to normal operation with the programmed input types Basic Connections All connections are made to removable screw ter...

Страница 7: ...orage temperature range 40 to 85 C Relative humidity 0 to 90 non condensing Connections Removable screw terminal blocks for 12 to 22 AWG wire Enclosure 1 8 DIN high impact plastic UL 94V 0 front color...

Страница 8: ...only by trained service personnel Installation There is no need to remove the instrument from its case to complete the installation wiring and setup Unpacking Remove the instrument from box Inspect th...

Страница 9: ...0 C or 60 75 C insulation for all line voltage connections Observe all safety regulations Electrical wiring should be performed in accordance with all applicable national state and local codes to prev...

Страница 10: ...eparate in put channel and all emitters connected to common All channels are factory set for transistor inputs normally in the cutoff or off state For normally active saturation state or on transistor...

Страница 11: ...nputs OC or TTL signals However throughout this manual the term pushbutton is used to describe these external inputs Please refer to the chart below for signal logic External Input Type Active When Sw...

Страница 12: ...ISA sequences A F1A and F2A which reset acknowledged channels automatically See selected sequence details for complete function description see Full Sequence Descriptions page 17 LED TEST SILENCE ACK...

Страница 13: ...ition Alarm Conditions for normally closed inputs 1 An open contact between an input channel and common will cause an alarm condition 2 An off or cutoff state transistor between an input channel and c...

Страница 14: ...cleared Relay Fail Safe In fail safe operation a relay coil is energized in non alarm condition In case of power failure relays will go to alarm state Fail safe operation is set independently for eac...

Страница 15: ...ton enable disable option see page 15 and no lock in option see page 16 Relay Operation Overview The following figure illustrates the operation of the relays ACK Pressed ON OFF Relay 1 ON OFF Relay 2...

Страница 16: ...conds to return to operation The green power LED will blink quickly to indicate the unit is in the advanced programming mode The unit will automatically leave setup mode if no pushbutton is pressed fo...

Страница 17: ...The input is in alarm state and the channel has not been acknowledged with the ACK pushbutton Acknowledge The alarm state is acknowledged with the ACK pushbutton This will restart the first out indica...

Страница 18: ...dge Steady Steady Off Normal Off Off Off Condition LED Horn 1st Pt Next Pt Normal Off Off Off Alert Flash Steady On Normal Flash Off On ACK Pushbutton Acknowledge Off Off Off Condition LED Horn 1st Pt...

Страница 19: ...al Off Off Off Alert Intermittent Flash Fast Flash On RESET Pushbutton 1st Out Reset Fast Flash Fast Flash On ACK Pushbutton Acknowledge Steady Steady Off Normal Off Off Off Maintained Alarm ACK befor...

Страница 20: ...Flow Chart Condition LED Horn Normal Off Off Alert Steady On Normal Off Off Condition LED Horn Normal Off Off Alert Flash On Normal Flash On ACK Pushbutton Acknowledge Steady Off RESET Pushbutton Rese...

Страница 21: ...ledge Steady Steady Off RESET Pushbutton Reset Off Off Off Condition LED Horn 1st Pt Next Pt Normal Off Off Off Alert Flash Steady On ACK Pushbutton Acknowledge Steady Steady Off Normal Steady Steady...

Страница 22: ...echnical standards and when applicable or required a European Union notified body certification Standards EN 55022 2003 EN 61000 6 2 2001 EN 61010 1 2001 EN 61326 2006 The standards EN 55022 2003 EN 6...

Страница 23: ...PD154 PD158 Vigilante II Annunciators Instruction Manual 23 This page left blank intentionally...

Страница 24: ...www predig com LIM158_F SFT043 Ver 1 0 up 05 20 Contact Precision Digital Technical Support Call 800 610 5239 or 508 655 7300 Fax 508 655 8990 Email support predig com Sales Support Call 800 343 1001...

Отзывы: