5.11  ELECTRIC LOCK 

There is an output (EL) for the electric lock 12V max 15VA. The command is given before every opening 
manoeuvre for 2 seconds, and before every re-opening caused by the triggering of a photocell or safety device. 
Using dip-switch 4 on the card, the kick-back and the final stroke at the end of the closing manoeuvre can be 
enabled or not. 
Dip-switch 4 in ON position: kick-back and final stroke enabled 
Dip-switch 4 in OFF position: kick-back and final stroke disabled. 

5.12  COURTESY LIGHT 

Using the LCU expansion card a courtesy light can be managed. The contact given by the LCU card is clean 
and allows a 230VAC max.500W lamp to be managed. The command to switch on the courtesy light is given 
before every manoeuvre and the contact remains activated for about 120 seconds from opening. 

5.13  LOGICAL STOP (STP INPUT) 

The activation of the STOP input stops all the functions. 
To resume the cycle the STOP must be deactivated and another command given. 

5.14  CONTROL UNIT MEMORY FAULT 

The EEPROM memory contains the control unit operating parameters, the codes, the logic and the memory of 
the radio receiver. When the control unit is turned on, should there be a fault in the EEPROM memory, the red 
LED flashes and all manoeuvres are blocked.
 
The Reset function must be executed (press and hold the programming button P1/SET for 2 seconds, until the 
yellow LED flashes). 
If the red  LED turns of, the EEPROM is good, but all  programming of parameters and  learning of transmitters 
must be done again. 
If the red LED still flashes, an authorised service centre should be contacted. 

6.  SIGNALLING LED 

 

Yellow led SET: 

-  flashes  for  5  seconds  when  turned  on  to  indicate  that  it  is  possible  to  enter  the  Professional  or  Simplified 

Learning modes. 

- lights up with a fixed light while Professional or Simplified Learning are carried out. 
- is turned off when the control unit functions normally. 
Red led ER: 
- is turned off during normal control unit operations 

is alight (fixed light) when the control unit is blocked because it has failed the safety test or there is a TRIAC in 

short circuit or a motor is disconnected 
Red led RAD: 
- flashes briefly when a 433 MHz Multipass radio code is received 
- is alight (fixed light) when radio codes are being memorised 
- flashes rapidly when the control unit is switched on and the radio code memory is defective 
- flashes rapidly during the cancellation of radio codes 
- flashes slowly when there is an attempt to memorise new radio codes and the memory is full 
- is switched off when the control unit is functioning normally and waiting to receive a command via radio. 
Green led GC: 
-  is alight (fixed light) when the automation is completely closed 
- flashes during the closing manoeuvre 
- otherwise it is switched off 
Red led GO: 
- is alight (fixed light) when the automation is open. 
- flashes during the opening manoeuvre 
- otherwise it is switched off 
Red led PH: 
- is alight when the photocell (PHO input) is aligned 
- is switched off when the photocell (PHO input) is not aligned 
Red led ST: 
- is alight when the STOP (STP) input is closed 
- is switched off when the STOP (STP) input is open. 
Green led START: 
- is alight when the OPEN/STEP/STEP (STR) input is closed
- is switched off when the OPEN/STEP/STEP (STR) input is open
 

Intelligent Security & Fire Ltd.

Содержание UNIK2E230

Страница 1: ...it Prastel S p A declines any responsibility in the event current standards in the country of installation are not complied with The symbol CE conforms with European Directive R TTE 99 05CE ELECTRONIC CONTROL PANEL FOR TWO 230VAC MOTORS UNIK2E230 _ V2 COMPLETE UNIK2E230SK _ V2 WITHOUT BOX AND TRANSFORMER BOX IP 54 I n t e l l i g e n t S e c u r i t y F i r e L t d ...

Страница 2: ...ERATION OF THE SAFETY DEVICES 8 5 3 TRIMMER FOR MOTOR SPEED 9 5 4 TRIMMER DEL DELAY BETWEEN MOTORS 9 5 5 TRIMMER PAU OPENING AND CLOSING OPERATING MODE 9 5 6 PEDESTRIAN OPENING FUNCTION 11 5 7 TRIMMER OBS OBSTACLE SENSITIVITY DETECTION 11 5 8 FLASHING LIGHT 11 5 9 GATE OPEN WARNING LIGHT 11 5 10 SLOW DOWN 11 5 11 ELECTRIC LOCK 12 5 12 COURTESY LIGHT 12 5 13 LOGICAL STOP STP INPUT 12 5 14 CONTROL U...

Страница 3: ...ing a trimmer Customisable partial opening for pedestrian transit 0 to 60 stand by time adjustment via trimmer 0 1 to 3 0 obstacle detection triggering time adjustment via trimmer Initial settings using dip switches Signalling LEDs 8 Expansion for electric lock 12V 15W max optional board ELU with optional relay Expansion for courtesy light optional board LCU Built in 433MHz rolling code receiver w...

Страница 4: ...mmended set the Force to 100 FOR trimmer completely clockwise do not use the slow down carry out the professional learning procedure do not use the obstacle detection trimmer OBS to MAX i During the learning with no electric limit switches present and with the obstacle detection disabled e g with hydraulic operators or else with no mechanical STOP strike plate present to define the manoeuvre times...

Страница 5: ...UNIK2E230 V2 ENGLISH ISUNIK2E230v2_GB_10_12 doc 5 4 1 GENERAL DIAGRAM OF SETTINGS AND CONNECTIONS 30 31 32 33 34 I n t e l l i g e n t S e c u r i t y F i r e L t d ...

Страница 6: ... Description DIP STAUS Operation 1 2 CH RAD See pag 8 OFF OFF Button 1 of the TX enabled OFF ON Button 2 of the TX enabled ON OFF Button 3 of the TX enabled ON ON Button 4 of the TX enabled 3 FAST See pag 10 OFF Rapid re closing disabled ON Rapid re closing enabled 4 STRIKE See pag 12 OFF Lock stroke disabled ON Lock stroke enabled 5 LAMP See pag 11 OFF Flashing light fixed ON Flashing light flash...

Страница 7: ...t from 1 Control unit starts pedestrian opening Press P1 SET or button 1 of the remote control to stop pedestrian opening Press P1 SET or button 1 of the remote control NO YES only by wire Photocell PHO in closing must Press P2 RAD or button 2 of the remote control Opening slow down Pedestrian function Safety intervention in closing Safety intervention in opening The EDG safety in opening must Sto...

Страница 8: ... press and release the RPA learning pushbutton also see the instructions of the TX used Carry out this operation 5 6 metres from the receiver the LED signals the activation Transmit by pressing one of the channel pushbuttons of the new transmitter to be enabled Enable all the new transmitters by pressing a pushbutton on each one of them The exit from the procedure occurs automatically 10 seconds a...

Страница 9: ...unter clockwise the speed of the motor if 50 of the maximum speed With the trimmer at half travel the speed of the motor if 75 of the maximum speed ATTENTION Changing the setting of trimmer FOR requires repeating the learning procedure since the travel times and the slow down start times change EXAMPLE Force Speed 50 EXAMPLE Force Speed 75 EXAMPLE Force Speed 100 5 4 TRIMMER DEL DELAY BETWEEN MOTO...

Страница 10: ...rimmer is turned fully counter clockwise with a 2 nd motor delay of 3 seconds for all the other positions of the DEL trimmer the opening terminates when the limit switch or the obstacle detection device are triggered the manoeuvre time has elapsed or there is a radio or manual command In the latter case the control unit disables the automatic closing and to restart the manoeuvre a further command ...

Страница 11: ... sec If the OBS trimmer is in the MAX position the obstacle detection is disabled If electric limit switches are present the obstacle detector will provoke an inversion of the motion in closing and a 2 second inversion in opening If there are no electric limit switches the obstacle detector provokes in closing an inversion of the motion unless it is in the last five seconds of the manoeuvre where ...

Страница 12: ... the red LED still flashes an authorised service centre should be contacted 6 SIGNALLING LED Yellow led SET flashes for 5 seconds when turned on to indicate that it is possible to enter the Professional or Simplified Learning modes lights up with a fixed light while Professional or Simplified Learning are carried out is turned off when the control unit functions normally Red led ER is turned off d...

Страница 13: ...the current available for the accessories Control Unit Transformer Power Power absorbed by the control unit Power available for the accessories Voltage of the accessories Current available for the accessories UNIK2E230 20VA 6 4W 13 6W 24V 560mA The following table shows the average absorption of the most common Prastel VDS accessories Product Absorption Photocell FOTO30SDE couple TX RX 50 mA Photo...

Страница 14: ... control The remote control has not been memorised or is broken or the battery is flat Check change the battery Carry out the remote control acknowledgement procedure The electrical limit switch activates but the motor does not stop The opening and closing limit switches have been exchanged An NO contact has been used instead of an NC Check the connections The gate moves then stops both in opening...

Страница 15: ...r and by current legislation All installation maintenance repairs and cleaning operations must be documented This documentation must be preserved by the user and made available to the personnel responsible for the control WARNINGS FOR THE USER Read the instructions and enclosed documentation carefully The product must be used for the express purpose for which it was designed Any other use is consi...

Отзывы: