General Information
Owner’s Manual for 50 Hz Air-Cooled Generator Sets
13
Specifications
Generator Set
Model
20 kVA
Rated voltage
400
Alternate voltage
380 / 416
Power factor
0.8
Rated maximum load current (amps) at rated voltage*
28.9
Maximum load current (amps) at alternate voltage*
30.1 / 27.18
Main circuit breaker
32 A
Phase
3
Rated AC frequency
50 Hz
Battery requirement
Group 26R, 12 Volts and 540CCA Minimum
(See
Enclosure
Aluminum
Weight (kg / lb)
207 / 457
A-Weighted sound pressure level (LpA) at 1 m (3.3 ft)
80 dB(A)
Sound pressure measurement uncertainty
1 dB(A)
A-Weighted sound power level (LwA)
94 dB(A)
Sound power measurement uncertainty
1 dB(A)
Normal operating range
This unit is tested in accordance to ISO 8528 standards
with an operating temperature of -29 °C (20 °F) to 50 °C
(122 °F). For areas where temperatures fall below 0 °C
(32 °F), a cold weather kit is recommended. There may
be a decrease in engine power when operated above
25 °C (77 °F). See engine specifications section.
These generator sets are rated in accordance with ISO 8528, Reciprocating Internal Combustion Engine Driven Alternating Current Generating
Sets–Safety.
* Natural gas ratings will depend on specific fuel joules (BTU) content. Typical derates are between 10–20% off the LP gas rating.