TROUBLE SHOOTING:

WHILE MACHINE IS UNDER WARRANTY, CHECK WITH SUPPLIER BEFORE DISMANTLING ANY PART OF THE GENERATOR ASSEMBLY.

NO OUTPUT VOLTAGE FROM SOCKETS:

IS THE VOLTAGE SELECTOR SWITCH 'ON'

YES

IS THE CIRCUIT-BREAKER and/or ELCB 'ON'

YES

        CAPACITOR CONTROLLED MACHINES

GAIN ACCESS TO REAR OF SOCKET PANEL,

THERE IS AN ALTERNATOR FAULT. LOCATE THE

IS THERE VOLTAGE FROM ALTERNATOR LEADS 

NO

CAPACITOR AND, WITH MACHINE RUNNING, 

YES

ENERGIZE WITH 12 VOLT BATTERY, IS MACHINE 

THERE IS A FAULT ON THE PANEL, CHECK

NOW WORKING

CONNECTIONS AND CONTINUITY IN SWITCH 

NO

AND CIRCUIT BREAKER

DISCONNECT LEADS FROM CAPACITOR AND

CHECK RESISTANCE ACROSS LEADS, DOES

THE VALUE AGREE WITH THAT IN ALTERNATOR

HAND BOOK

              A.V.R.CONTROLLED MACHINES

NO

THERE IS AN ALTERNATOR FAULT.

YES

  STATOR MUST BE

REMOVE THE EXCITATION LEADS FROM THE 

  REPLACED

A.V.R.AND MEASURE WINDING RESISTANCE, 

DISMANTLE ALTERNATOR

DOES THE VALUE AGREE WITH THAT IN

    AND CHECK DIODES

NO

 REPLACE FAULTY

ALTERNATOR HAND BOOK

       ARE THEY O.K.

NO

YES

YES

REPLACE EXCITER

CHECK ROTOR RESISTANCE

STATOR

IS IT O.K.

YES

NO

ENERGISE THE EXCITATION LEADS WITH A 12 VOLT

  STATOR MUST BE

     ROTOR MUST BE 

BATTERY, OBSERVING THE CORRECT POLARITY 

  REPLACED

     REPLACED

DOES THE MACHINE NOW  GIVE ABOUT THE RIGHT

VOLTAGE OUTPUT.

YES

REPLACE A.V.R. BOARD

NO

IS THE VOLTAGE EQUAL FOR EACH PHASE

YES

NO

PROBABLE ROTOR FAULT,

PROBABLE STATOR FAULT,

DISMANTLE AND CHECK 

DISMANTLE AND CHECK FOR

RESISTACES AND DIODES,

BURNT OR BROKEN WIRES,

REPLACE WHERE NECESSARY

REPLACE WHERE NECESSARY

NO BATTERY CHARGER OUTPUT:

YES

IS THE MACHINE RUNNING AT THE

YES

LOCATE THE BATTERY CHARGE 

RECTIFIER, IS THERE DC VOLTAGE

NO

IS THERE AC VOLTAGE AT THE

FROM OUTPUT TERMINALS

 RECTIFIER INPUT TERMINALS

YES

   YES

NO

THERE IS A WIRING FAULT FROM

REPLACE

STATOR MUST

RECTIFIER TO OUTPUT AT PANEL,

RECTIFIER

BE REPLACED

USE MULTIMETER TO CHECK
CONTINUITY OF WIRING

IF PROBLEM CANNOT BE SOLVED, CONTACT SUPPLIER'S SERVICE DEPARTMENT

ENGINE WILL NOT START:

ASSUMING, ON ELECTRIC START MACHINES, THAT THE STARTER MOTOR WORKS OK. 

FIRST CHECK THE FOLLOWING:

IS THERE FUEL IN THE TANK

IS THE CHOKE ON *

IS THE FUEL TAP ON

IS THE SPARK PLUG WORKING *

IS THERE OIL IN THE SUMP

HAS THE PRE-HEAT 

BEEN OPERATED

ENSURE THERE IS NO

WATER IN THE FUEL

DOES THE FUEL SYSTEM

NEED 'BLEEDING TO 

* PETROL MACHINES ONLY

REMOVE AIR

IF PROBLEM CANNOT BE SOLVED, CONTACT ENGINE SERVICE AGENT

         DIODE

CORRECT SPEED

IS THE FUSE/CIRCUIT BREAKER OK.

Содержание E5000

Страница 1: ...1 GENERATOR USE AND MAINTENANCE MANUAL HG2500 E3200 E4000 E5000 E6900 ...

Страница 2: ...e engine due to restricted air flow The generator must be operated on a level surface The generator should be anchoured securely if there is a risk of movement i e units with unbraked chassis frames should be chocked Do not replenish fuel or oil while the generator is running Do not allow unauthorised persons or children in the work area even after the machine has stopped there is a risk of severe...

Страница 3: ...3 A B C D ...

Страница 4: ...required and is either on the frame or on the electric panel NOISE LEVEL LABEL REGISTERED NUMBER This certifies that the equipment will not exceed the This label indicates the name registered number and the relevant figure shown on the label The label is located characteristics of the machine The label is located on the tubular frame or on the front panel of the machine on the casing of the machin...

Страница 5: ...companies Cables plugs sockets and cable couplers should be suitable for the environmental conditions Cables should be preferably flexible and contain a metallic screen Plugs and sockets should conform to BS4343 If metallic screen cable is not available a cable with high abraison resistance with a separate protective conductor should be utilised Cables should be as short as practicable and routed ...

Страница 6: ... generator cannot turn over during transportation Remove all fuel and ensure that acid or fumes do not leak from the battery where applicable Do not overload the transport vehicle Under no circumstances should the generator be started while inside a truck The generator is a heavy item movement is to be carried out under the guidelines of the Health Safety At Work Act Lifting eyes where fitted are ...

Страница 7: ... VOLT STATOR MUST BE ROTOR MUST BE BATTERY OBSERVING THE CORRECT POLARITY REPLACED REPLACED DOES THE MACHINE NOW GIVE ABOUT THE RIGHT VOLTAGE OUTPUT YES REPLACE A V R BOARD NO IS THE VOLTAGE EQUAL FOR EACH PHASE YES NO PROBABLE ROTOR FAULT PROBABLE STATOR FAULT DISMANTLE AND CHECK DISMANTLE AND CHECK FOR RESISTACES AND DIODES BURNT OR BROKEN WIRES REPLACE WHERE NECESSARY REPLACE WHERE NECESSARY NO...

Страница 8: ...ar NP22 4EF Telephone 44 01495 713300 Fax 44 01495 718766 e mail info pramac co uk website www pramac com No Modifications Are Allowed To This Document Unless Prior Approval Has Been Received And Approved By The Technical Department cod G005471 01 2005 REV 01 ...

Отзывы: