4. PRELIMINARY CHECKS: 
- Make sure these operations are carried out with the generator placed on a horizontal and stable surface. 
- Oil is the most important element influencing the efficiency and life of the engine, the engine manual gives details of the type of oil to 
use and the correct oil level for this generator. 
ATTENTION: Running the engine with insufficient oil could cause serious damage. 
- Check the fuel level: use only clean and water-free fuel (it is better to use lead-free petrol or petrol with a low lead content, in order to 
minimize the deposits in the combustion chamber). 
ATTENTION: Fuel is highly inflammable and explosive under certain conditions. 
Refuel in a well ventilated area with the engine switched off, do not smoke or approach the equipment with an open flame.  
Do not overfill the tank (do not fill up to the cap), because vibration could cause fuel spillage.  
Avoid  spilling  fuel  while  filling  the  tank.  Ensure  that  the  cap  is  correctly  screwed  down  after  filling.  If  fuel  has  been  spilt, 
ensure that the area is completely dry before starting the engine.  
Avoid  any  skin  contact  with  the  fuel  and do not inhale the vapour. It is important to keep the fuel in a place inaccessible to 
children. The fuel fumes are highly inflammable. 
- Check the air filter: make sure that it is in good condition and free from dust and dirt. To locate the filter consult the engine manual. 
ATTENTION: do not use the generator without the air filter: the life of the engine and the generator will be reduced! 
-  Activate  the  battery:  fill  the  compartments  to  their maximum level with a 30/40% sulphuric acid solution and wait at least two hours 
before using. 
ATTENTION:  do  not  touch  the  acid  and  do  not  smoke  or  use  naked  lights:  battery  fumes  are  highly  inflammable.  Keep  the 
acid out of reach of children. 

5. STARTING THE GENERATOR:
- Ensure that no appliance is plugged into the generator. 
- For generators with electric starters turn the key to the “START” position and release it as the machine starts. 
- To start the recoil operated generators, turn choke to on position, pull the cord handle until resistance is felt, then pull energetically. 
ATTENTION: Do not allow the recoil  handle to rewind quickly, feed back manually to avoid damage to the starter. 
When the engine has warmed up, turn off the choke, the generator is now ready for use. – 
- For Yanmar diesel engines refer to label located on rear of tank for starting procedure. 
NOTE:  If  the  generator  is  used  at  high  altitudes  or  temperatures,  the  air-fuel  mix  ratio  may  be  too  rich;  this  will  cause  higher 
consumption and lower performance. Check the effective power of the generator by means of the following correction factors: 
HEIGHT: Power diminishes on average by 1% for every 100 m of height above sea level; 
TEMPERATURE: Power diminishes on average by 2% for every 5 degrees centigrade of temperature above 20 degrees centigrade. If 
the generator is used above an altitude of 2000 m, consult the manufacturer for advice on the fuel mix for best performance. 

6. USING THE GENERATOR:
NOTE: The generator is built to current standards and has been designed to satisfy a very wide range of applications. 
It  should  be  remembered  that  every  application  is  subject  to  specific  electrical,  accident  prevention  and environmental standards; for 
this reason the generator should be considered as an integral part of the complete installation, which should be designed, tested and 
approved by qualified technicians and/or companies.
 - Cables plugs, sockets and cable couplers should be suitable for the environmental conditions.  Cables should be preferably flexible, 
and contain a metallic screen. Plugs and sockets should conform to BS4343.  If metallic screen cable is not available, a cable with high 
abraison resistance, with a separate protective conductor should be utilised.  Cables should be as short as practicable, and routed to 
avoid possible accidental damage.  All cables, plugs, sockets and connectors should be inspected regularly. 
-  Industrial and hand-held tools(110v) and domestic portable electrical equipment(220v) should preferably of Class II construction. 
-  NEVER overload sockets ! Maximum outputs are :- 
   110v – 16amp Socket 2KW, 32amp Socket 4 KW  :  220v – 16amp Socket 4KW, 32amp Socket 8KW.  
-  In  order  to avoid electrical accidents, all connections to the distribution panel must be carried out by qualified technicians. Incorrect 
connections can harm people and damage the generator. 
Protection  against  electric  shock:  all  generators  rely  on  their  electrical  insulation,  however,  on  request,  they  can  be  supplied  with 
various  additional  protection  options  e.g.  earth  leakage  breaker,  insulation  monitor  (isometer),  or  they  can  be  protected  in  the  same 
way during installation by the user. 
It is important therefore, to follow the instructions as below: 
1)  Standard  generator:  protected  by  electrical  insulation.  This  equipment  has  a  thermal  protection  device  and/or  a  thermomagnetic 
device to protect against a current surge, overload or short-circuit. This is known as a ‘floating’ system. 
In this case the generator winding must not be earthed using the terminal "PE" or with any other part of the generator. 
2)  Generator  with  optional  switchboard  (or  with  other  devices  installed  by  the  user):  must  be  protected  using  a  circuit  breaker'  which 
automatically cuts off the power supply. 
This  has  thermal  overload  protection  devices  and/or  thermomagnetic  combinations  with  earth-leakage  circuit  breakers  or  insulation 
monitors  (isometer),  which  automatically  cut  off  the  power  supply  in  the  event  of  a  breakdown  of  the  insulation.  When  fitted  with  an 
earth leakage breaker the unit must be earthed using the PE terminal. If an isometer is fitted this connection is NOT required. 
IMPORTANT: In the event of the user installing earth-leakage circuit-breakers, it is important for its correct functioning that: 
A)  For  single  phase  generators  the  neutral  of  the  output  must  be  connected  to  earth.  B)  For  three  phase  generators  the 
neutral (star point) should be connected to earth. 
In the case of a three phase delta connection, it is not possible to install an earth-leakage circuit-breaker. 
Contact our technical office for further information if required. 

-

 

The  generator  is  provided  with a PE connection screw to ensure that the unit can be earthed as shown by the label, which also 
ensures that all metal parts of the generator are simultaneously earthed. 

-

CTE (Centre Tapped to Earth) generators should be earthed at all times. 

- Do not connect accessories with unknown electrical specifications to the generator. 
-  The  electrical  circuit  of  the  generator  is  protected  by  a  switch,  which  is  either  thermomagnetic,  earth-leakage-thermomagnetic  or 
thermal,  an overload or a short circuit will cut off the flow of current. 
To reset, disconnect all appliances, check the cause of the short-circuit or overload and switch back on. 
- If using the generator as a battery charger, place the battery at least 1 m from the unit, making sure that the filling plugs are removed 
from the cells. 
- Take care to observe the battery polarities, incorrect connection of positive and negative poles could cause the battery to explode. 

Содержание E5000

Страница 1: ...1 GENERATOR USE AND MAINTENANCE MANUAL HG2500 E3200 E4000 E5000 E6900 ...

Страница 2: ...e engine due to restricted air flow The generator must be operated on a level surface The generator should be anchoured securely if there is a risk of movement i e units with unbraked chassis frames should be chocked Do not replenish fuel or oil while the generator is running Do not allow unauthorised persons or children in the work area even after the machine has stopped there is a risk of severe...

Страница 3: ...3 A B C D ...

Страница 4: ...required and is either on the frame or on the electric panel NOISE LEVEL LABEL REGISTERED NUMBER This certifies that the equipment will not exceed the This label indicates the name registered number and the relevant figure shown on the label The label is located characteristics of the machine The label is located on the tubular frame or on the front panel of the machine on the casing of the machin...

Страница 5: ...companies Cables plugs sockets and cable couplers should be suitable for the environmental conditions Cables should be preferably flexible and contain a metallic screen Plugs and sockets should conform to BS4343 If metallic screen cable is not available a cable with high abraison resistance with a separate protective conductor should be utilised Cables should be as short as practicable and routed ...

Страница 6: ... generator cannot turn over during transportation Remove all fuel and ensure that acid or fumes do not leak from the battery where applicable Do not overload the transport vehicle Under no circumstances should the generator be started while inside a truck The generator is a heavy item movement is to be carried out under the guidelines of the Health Safety At Work Act Lifting eyes where fitted are ...

Страница 7: ... VOLT STATOR MUST BE ROTOR MUST BE BATTERY OBSERVING THE CORRECT POLARITY REPLACED REPLACED DOES THE MACHINE NOW GIVE ABOUT THE RIGHT VOLTAGE OUTPUT YES REPLACE A V R BOARD NO IS THE VOLTAGE EQUAL FOR EACH PHASE YES NO PROBABLE ROTOR FAULT PROBABLE STATOR FAULT DISMANTLE AND CHECK DISMANTLE AND CHECK FOR RESISTACES AND DIODES BURNT OR BROKEN WIRES REPLACE WHERE NECESSARY REPLACE WHERE NECESSARY NO...

Страница 8: ...ar NP22 4EF Telephone 44 01495 713300 Fax 44 01495 718766 e mail info pramac co uk website www pramac com No Modifications Are Allowed To This Document Unless Prior Approval Has Been Received And Approved By The Technical Department cod G005471 01 2005 REV 01 ...

Отзывы: