6333V103-IN
13
6333QA01
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM
Revision date:
2009-09-29
Version Revision
V1R0
Page:
1/1
ATEX Installation drawing
6333
For safe installation of 6333B the following must be observed. The module shall only be installed by
qualified personnel who are familiar with the national and international laws, directives and
standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.
.
ATEX Certificate KEMA 09ATEX 0147
Marking
Standards
EN 60079-0 : 2006, EN 60079-11 : 2007, EN 60079-26 : 2007
Installation notes.
The instructions provided with the equipment shall be followed in detail in order to
assure safe operation.
Non Hazardous Area
Hazardous area
Zone 0, 1, 2
II 1 G Ex ia IIC T6..T5
Terminal:
41,42,43
Uo: 27 VDC
Io: 7 mA
Po: 45 mW
Lo: 35 mH
Co: 90 nF
Terminal:
11,13 and
21,23
Ui: 30 VDC
Ii: 120 mA
Pi: 0.84 W
Li: 10
μ
H
Ci: 1.0nF
T5: -40
≤
Ta
≤
60ºC
T6: -40
≤
Ta
≤
40ºC
Terminal:
51,52,53
Uo: 27 VDC
Io: 7 mA
Po: 45 mW
Lo: 35 mH
Co: 90 nF
13
11
43
42
43
+
-
Barrier
23
21
53
52
51
+
-
Barrier
6333
CH2
CH1
CONTENTS