6
6
333V103-IN
Effect of supply voltage variation ................
≤
0.005% of span / VDC
Max. wire size .............................................. 1 x 1.5 mm
2
standed wire
Humidity ...................................................... < 95% RH (non-cond.)
Dimensions (H x W x D) .............................. 109 x 23.5 x 104 mm
Protection degree ........................................ IP20
Weight (1 / 2 channels) ................................ 145 / 185 g
Electrical specifications, inputs:
Max. offset................................................... 50% of selec. max. value
RTD and linear resistance inputs:
Cable resistance per wire (max.) ................. 10
Ω
Sensor current ............................................. > 0.2 mA, < 0.4 mA
Effect of sensor cable resistance
(3-wire) ......................................................... < 0.002
Ω
/
Ω
Sensor error detection ................................ Yes
Outputs
:
Current outputs
:
Signal range ................................................ 4...20 mA
Min. signal range ......................................... 16 mA
Updating time .............................................. 135 ms
Load resistance ...........................................
≤
(V
supply
- 8) / 0.023
[Ω]
Load stability ............................................... < ±0.01% of span / 100
Ω
Sensor error detection:
Programmable ............................................. 3.5...23 mA
NAMUR NE43 Upscale ............................... 23 mA
NAMUR NE43 Downscale ........................... 3.5 mA
Of span = Of the presently selected range
RTD
type
Min.
value
Max.
value
Min.
span
Standard
Pt100
Ni100
Lin. R
-200°C
-60°C
0
Ω
+850°C
+250°C
10000
Ω
25°C
25°C
30
Ω
IEC 60751
DIN 43760
-----
Basic values
Input type
Basic
accuracy
Temperature
coefficient
RTD
≤
±0.3°C
≤
±0.01°C/°C
Lin. R
≤
±0.2
Ω
≤
±20 m
Ω
/ °C
EMC immunity influence ................................ < ±0.5% of span
CONTENTS
CONTENTS