Version No. V3R0
9
9203 Solenoid / Alarm Driver
Safety Manual
14.2.2 if password is set
action
display shows
1
Press OK
PASSW
2
Enter password and press OK
ADV.SET
3
Set (ADV.SET) to Yes and press OK
DISP SETUP
4
Step down to (SIL SETUP) and press OK
EN.SIL
5
Set (EN SIL) to YES and press OK
(At this time the device starts operating in
SIL mode with the entered configuration
parameters!)
Verify
OPEN
”briefly”
LOCK*
6
Press OK to confirme verification of the
OPEN-LOCK in the display
CH1.FUN
7
Verify Channel 1 function and press OK
CH2:FUN
8
Verify Channel 2 function and press OK
PASSW
9
Verify password and press OK
SIL.OK
10
Verify SIL and press OK
* Open is shown briefly in the display
14.3 functional test
The user is responsible for making a functional test after verification of
safety parameters. The procedure for periodic proof test described in
section 10 shall be used.
15. fault reaction and restart condition
When the 9203 detects a fault the output will go to Safe State, in which the
safety output will go to ”de-energised”.
For device faults there are 2 ways of bringing the device out of Safe State.
1. Power cycle the device.
2. Bring the device out of SIL mode (choose “NO” in the menu point ”EN.
SIL”), and set it back to SIL mode again (choose “YES” in the menu point
“EN.SIL” and verify the configuration).