9106 - Product Version 9106-001
9
Order codes
9106B1A = HART
®
Transparent Repeater, 1 channel
U
o
28 VDC (max. loop voltage)
9106B2A = HART
®
Transparent Repeater, 1 channel
U
o
25.6 VDC (max. loop voltage)
9106B1B = HART
®
Transparent Repeater, 2 channels
U
o
28 VDC (max. loop voltage)
9106B2B = HART
®
Transparent Repeater, 2 channels
U
o
25.6 VDC (max. loop voltage)
4501
= Display / programming front
9400
= Power rail
Electrical specifications
Specifications range .................................... -20...+60°C
Storage temperature ................................... -20...+85°C
Common specifications:
Supply voltage, DC ..................................... 19.2...31.2 VDC
Max. consumption, 2 channels ................... < 3 W
Fuse ............................................................. 1.25 A SB / 250 VAC
Isolation:
Input to any .......................................... 300 VAC double / reinforced isolation
Analogue output to supply................... 300 VAC double/reinforced isolation
Status relay to supply .......................... 150 VAC double/reinforced or
300 VAC basic isolation
Communications interface .......................... Programming front 4501
HART
®
communication, frequency range ... 0.5...2.5 kHz, 2-way
Signal / noise ratio ...................................... Min. 60 dB (0.5...10 kHz)
Response time (0...90%, 100...10%) .......... < 5 ms
Calibration temperature............................... 20...28°C
Effect of supply voltage change on output
(19.2...31.2 VDC, nom. 24VDC) ................... < ±10 µA
CONTENTS