9106 - Product Version 9106-001
35
9106QF01
LERBAKKEN 10, 8410 RØNDE DENMARK
Revision date:
2011-11-02
Version Revision
V3 R0
Prepared by:
PB
Page:
4/5
Simple Apparatus or
Intrinsic safe apparatus
with entity parameters:
Vmax (Ui)
≥
Vt (Uo)
Imax (Ii)
≥
It (Io)
Pi
≥ Pt (Po)
Ca ≥ C
cable
+ Ci
La ≥ L
cable
+ Li
9106B1A, 9106B1B
Ex input: Loop current source 1 to 2
CH1 (terminal 44)
CH2 (terminal 52)
U
o
:
28 V
I
o
:
93 mA
P
o
:
0.65 W
IIC or A,B IIB or C,E,F
IIA or D,G
C
o.
0.08
µ
F
0.600
µ
F
2.15
µ
F
L
o.
3 mH
12 mH
25 mH
-20
≤
Ta
≤
+60ºC
(terminal 11,12,13,14)
(terminal 31,32,33,34)
(terminal 91,92,93,94,95)
U
m
: 253 V, max. 400 Hz
44
43
42
41
54
53
52
51
34
33
32
31
14
13
12
11
9106
4501
91 92 93 94 95
Power
Rail
CH1
CH2
+
-
T
9106B2A, 9106B2B
Ex input: Loop current source 1 to 2
CH1 (terminal 44)
CH2 (terminal 52)
U
o
:
25.6 V
I
o
:
100 mA
P
o
:
0.64 W
IIC or A,B IIB or C,E,F
IIA or D,G
C
o.
0.10
µ
F
0.800
µ
F
2.75
µ
F
L
o.
2 mH
9 mH
15 mH
Hazardous Classified Location Unclassified Location or
Class I/II/III, Division 1, Group A,B,C,D,E,F,G
Hazardous Classified Location
Zone 0,1, 2 Group IIC, IIB, IIA or Class I, Division 2, Group ABCD T4
Zone 20, 21
Class I Zone 2 Group IIC T4