8
6337V100-IN
Input specifications:
RTD input types:
Pt50, Pt100, Pt200, Pt500, Pt1000, Ni50, Ni100, Ni120, Ni1000
Cable resistance per wire (max.)
................. 50
Ω
Sensor current ............................................. Nom. 0.2 mA
TC input types:
Cold junction compensation (CJC):
Constant, internal or external via a Pt100 or Ni100 sensor
mV input:
Voltage input range ..................................... -800...+800 mV
Min. span ..................................................... 2.5 mV
Input resistance ........................................... 10 M
Ω
RTD
type
Min.
value
Max.
values
Min.
span
Standard
Pt100
Ni100
Lin. R
-200°C
-60°C
0
Ω
+850°C
+250°C
7000
Ω
10°C
10°C
25
Ω
IEC 60751
DIN 43760
-----
Type
Min.
temperature
Max.
temperature
Min.
span
Standard
B
E
J
K
L
Lr
N
R
S
T
U
W3
W5
0°C
-100°C
-100°C
-180°C
-200°C
-200°C
-180°C
-50°C
-50°C
-200°C
-200°C
0°C
0°C
+1820°C
+1000°C
+1200°C
+1372°C
+900°C
+800°C
+1300°C
+1760°C
+1760°C
+400°C
+600°C
+2300°C
+2300°C
100°C
50°C
50°C
50°C
50°C
50°C
50°C
100°C
100°C
50°C
50°C
100°C
100°C
IEC584
IEC584
IEC584
IEC584
DIN 43710
GOST 3044-84
IEC584
IEC584
IEC584
IEC584
DIN 43710
ASTM E988-90
ASTM E988-90