7501QF01 

LERBAKKEN 10, 8410 RØNDE DENMARK.       WWW.PRELECTRONICS.COM 

 

 

   

Revision date: 

2015-07-28 

 

      Version Revision 
               V1R0 

 

 

Page: 

5/5 

 

 

 

Explosion proof / Dust ignition proof installation. 

 

The enclosure must be installed such, that even in the event of rare incidents, ignition sources due to impact 

and friction, sparks are excluded. 

 

Unused cable entries must be sealed by approved sealing plugs. 

 

Certified cable and cable glands shall be used that are suitable for the application and correctly installed or 

the cables must be run in conduit. 

 

For an ambient temperature exceeding 70 °C, heat resistant cables and cable glands suitable for at least 

90°C shall be used. 

 

For process temperatures above 85°C or below -20/-40°C installer must verify by measurements that the 

service temperature of the 7501 module is held within this range taking worst conditions into account. 

 

  The display cover must be screwed all the way in and the safety catch must be fastened before operation. 

 

  Protection degree of IP 66 or TYPE4X  is only achieved if certified cable glands or conduit entry devices are 

used that are suitable for the application and correctly installed with sealing washers or Loctite sealant is 

added to the threads of the sensor, blanking elements and cable glands. 

 

  The enclosure must be connected to the potential matching line. 

   

  Warning. 

  Do not open display cover unless area is known to be safe. 

 

  For installation in Canada the following must be taken into account: 

   

All openings for conduit and sensor connection must be in NPT threads.  

   

For Class I Group A installation, conduit seal is required within 18 inches of the enclosure. 

     

For Class I Zone I installation, conduit seal is required within 18 inches of the enclosure. 

 

 

 

7501QF01 

LERBAKKEN 10, 8410 RØNDE DENMARK.       WWW.PRELECTRONICS.COM 

 

 

   

Revision date: 

2015-07-28 

 

      Version Revision 
               V1R0 

 

 

Page: 

4/5 

 

 

 

 

Explosion proof / Dust ignition proof installation: 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

6

5

4

3

+

-

Supply

7501

Hazardous area 

Class I, II, III Division 1, Groups ABCDEFG 

Class I Zone 1, Ex/AEx d IIC T6  

 

 

Non Hazardous Area 

Terminal: 1,2 

Umax: 35 VDC 

 

Terminal: 3,4,5,6 

Sensor: RTD or TC

 

T6:             

-20/-40 ≤ Ta ≤ 70ºC   

T5, T4: 

-20/-40 ≤ Ta ≤ 85ºC   

O-ring Sealings   

Silicone rubber:-40°C ≤Ta ≤ +85°C 

FKM rubber:    -20°C ≤Ta ≤ +85°C 

 

Protection: Indoor and Outdoor Type 4X or IP66 

 

7501QB01 

LERBAKKEN 10, 8410 RØNDE DENMARK.       WWW.PRELECTRONICS.COM 

 

 

   

Revision date: 

2015-09-16 

 

      Version Revision 
               V2R0 

 

 

Page: 

2/6 

 

 

 

  

   

Instalação do Ex ia  

Instruções de instalação gerais 

O circuito do sensor não é infalivelmente galvânico-isolado do circuito de saída de alimentação. 

Contudo, a isolação galvânica entre os circuitos é capaz de resistir a teste de tensão de 500Vac 

durante 1 minuto. 

 

O equipamento deve ser conectado à linha potencial correspondente 

 

Se o transmissor estiver fisicamente conectado a uma possível fonte de calor ou resfriamento, por 

exemplo, através da montagem de um tubo de processo ou sensor de temperatura, a temperatura 

no ponto de conexão deve estar entre a faixa de temperatura ambiente determinada no certificado 

ou neste manual. 

 

As entradas dos cabos e elementos de supressão devem ser usadas adequadamente para 

aplicação INMETRO, aprovada e instalada corretamente. 

 

Para instalação em zona 0 / EPL Ga, se aplicam as seguintes instruções: 

O transmissor deve ser instalado de modo que, mesmo em um evento raro de incidente, fontes de 

ignição devido a impactos e fricção, faíscas sejam evitadas. 

 

O grau de proteção do IP 54 de acordo com a IEC 60529 é alcançado se o certificado prensa-

cabos ou dispositivos de entrada de conduíte são usados e adequados para a aplicação e 

instalados corretamente. 

 

O grau de proteção do IP 68 de acordo com a IEC 60529 é apenas alcançado se o certificado 

prensa-cabos ou dispositivos de entrada de conduíte são usados e adequados para aplicação e 

instalados corretamente com selos de vedação ou selante Loctite adicionados para as linhas do 

sensor, elementos de supressão e prensa-cabos. 

 

   

Cuidado 

Cuidados especiais devem ser tomados para evitar o acúmulo de carga eletrostática no 

equipamento devido ao repetitivo processo de carregamento, por exemplo, fluído de líquidos em 

alta velocidade, pós ou partículas de plásticos transportados pelo ar e outras cargas eletrostáticas 

para a superfície. 

 

 

 

 

 

7501QB01 

LERBAKKEN 10, 8410 RØNDE DENMARK.       WWW.PRELECTRONICS.COM 

 

 

   

Revision date: 

2015-09-16 

 

      Version Revision 
               V2R0 

 

 

Page: 

1/6 

 

 

 

7501 Desenho de Instalação INMETRO 

 

Para instalação segura do 7501 o seguinte deve ser observado. O módulo deve ser instalado, 

apenas por pessoas qualificadas as quais estão familiarizadas com as normas nacionais e 

internacionais, diretrizes e padrões (IEC60079-14) que se aplicam a esta área. 

 

         Instalação Segura do Ex ia installation:

 

 

 

 Certificado            DEKRA 15.0014X  

 

Marca 

 

 

 

   

 

 

Normas :  ABNT NBR IEC 60079-0: 2013, ABNT NBR IEC 60079-11: 2013 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Áreas não perigosas 

Áreas Perigosas 

Zona 0, 1, 2, 20, 21, 22 

T4:  -40 ≤ Ta ≤ 85ºC  T100 ºC (7501A) 

T4:  -40 ≤ Ta ≤ 80ºC  T100 ºC (7501B) 

T5:  -40 ≤ Ta ≤ 60ºC  T100 ºC   

T6:  -40 ≤ Ta ≤ 45ºC  T100 ºC 

 

Ex ia IIC T6...T4 Ga 

Ex ia IIIC T100°C Da 

 

Terminal do 

sensor: 3,4,5,6 

Uo: 9.6 VDC 

Io:   28 mA 

Po:  67 mW 

Lo:  35 mH 

Co:  3.5 μF 

Terminal de 

alimentação: 1,2 

Ui: 30 VDC 

Ii:   120 mA 

Pi:  0.84 W 

Li:  0 μH 

Ci:  2 nF 

1

2

6

5

4

3

+

-

Barrier

7501

 

7501QB01 

LERBAKKEN 10, 8410 RØNDE DENMARK.       WWW.PRELECTRONICS.COM 

 

 

   

Revision date: 

2015-09-16 

 

      Version Revision 
               V2R0 

 

 

Page: 

3/6 

 

 

 

Instalação ic, Ex nA:

 

 

 

 Certificado           DEKRA 15.0014X  

 

Marca 

 

Ex nA IIC T6…T4 Gc 

 

 

Ex ic IIC T6…T4 Gc 

 

 

Ex ic IIIC T100°C Dc 

 

   

 

 

Normas:  ABNT NBR IEC 60079-0: 2013, ABNT NBR IEC 60079-15: 2012 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Terminal do 

sensor: 3,4,5,6 

Ex ic 

Uo: 9.6 VDC 

Io:   28 mA 

Po:  67 mW 

Lo:  45 mH 

Co:  28 μF 

Terminal de 

alimentação: 1,2 

Ex ic 

Ui: 35 VDC 

Li:  0 μH 

Ci:  2 nF 

Terminal de 

alimentação: 1,2 

Ex nA 

U : 35 VDC 

 

1

2

6

5

4

3

+

-

Supply

7501

Áreas perigosas 

Zona  2, 22 

Áreas não perigosas 

Ex nA 

 

Anel de vedação O : Silicone 

T4: -40 ≤ Ta ≤ 85ºC  T4  (7501A ) 

T4: -40 ≤ Ta ≤ 80ºC  T4  (7501B ) 

T6: -40 ≤ Ta ≤ 60ºC  T6 

 

Anel de vedação O : FKM 

T4: -20 ≤ Ta ≤ 85ºC   (7501A ) 

T4: -20 ≤ Ta ≤ 80ºC   (7501B ) 

T6: -20 ≤ Ta ≤ 60ºC   

Ex ic 

 

T4:  -40 ≤ Ta ≤ 85ºC  T100ºC (7501A ) 

T4;  -40 ≤ Ta ≤ 80ºC  T100ºC (7501B ) 

T6:  -40 ≤ Ta ≤ 60ºC  T85 ºC  

 

 

7501QB01 

LERBAKKEN 10, 8410 RØNDE DENMARK.       WWW.PRELECTRONICS.COM 

 

 

   

Revision date: 

2015-09-16 

 

      Version Revision 
               V2R0 

 

 

Page: 

5/6 

 

 

 

 

          Instalação tb, Ex d:

 

Certificado        DEKRA 15.0014X  

 

Marca 

 

 

 

   

 

Normas ABNT NBR IEC 60079-0: 2013, ABNT NBR IEC 60079-1: 2009,  

                              ABNT NBR IEC 60079-31:2014 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Áreas não perigosas 

Áreas perigosas 

Zona  1, 2, 21, 22 

Ex d IIC T6…T4 Gb 

Ex tb IIIC T100°C Db 

Terminal: 3,4,5,6 

Sensor: RTD ou TC

 

Terminal: 1,2 

Alimentação: 35 VDC 

 

1

2

6

5

4

3

+

-

Supply

7501

Ex d 

 

T4,T5:  -40 ≤ Ta ≤ 85ºC  (7501A ) 

T4,T5:  -40 ≤ Ta ≤ 80ºC  (7501B ) 

T6:       -40 ≤ Ta ≤ 70ºC   

 

Ex tb 

 

Anel de vedação O: Silicone 

-40 ≤ Ta ≤ 85ºC  T100°C  (7501A ) 

-40 ≤ Ta ≤ 80ºC  T100°C  (7501B ) 

-40 ≤ Ta ≤ 70ºC  T85°C 

 

Anel de vedação O: FKM 

-20 ≤ Ta ≤ 85ºC  T100°C  (7501A ) 

-20 ≤ Ta ≤ 80ºC  T100°C  (7501B ) 

-20 ≤ Ta ≤ 70ºC  T85°C 

 

7501QB01 

LERBAKKEN 10, 8410 RØNDE DENMARK.       WWW.PRELECTRONICS.COM 

 

 

   

Revision date: 

2015-09-16 

 

      Version Revision 
               V2R0 

 

 

Page: 

4/6 

 

 

 

Instalação icx, Ex nA: 

  

Para uma temperatura ambiente excedendo 70 ºC, cabos resistentes ao calor e prensa-cabos 

adequados para pelo menos 90 ºC devem ser usados. 

 

Se o transmissor estiver fisicamente conectado a uma possível fonte de calor ou resfriamento, por 

exemplo, através da montagem de um tubo de processo ou sensor de temperatura, a temperatura 

no ponto de conexão deve estar entre a faixa de temperatura ambiente determinada no certificado 

ou neste manual.  

 

As entradas dos cabos e elementos de supressão devem ser usadas adequadamente para a 

aplicação e instaladas corretamente. 

 

O equipamento deve ser conectado à linha potencial correspondente 

 

O torque aplicado no terminal de parafusos é no máximo 0.4 Nm em todos os terminais. 

 

O grau de proteção do IP 54 de acordo com a IEC 60529 é alcançado se o certificado prensa-

cabos ou dispositivos de entrada de conduíte são usados e adequados para a aplicação e 

instalados corretamente. 

 

O grau de proteção do IP 68 de acordo com a IEC 60529 é apenas alcançado se o certificado 

prensa-cabos ou dispositivos de entrada de conduíte são usados e adequados para aplicação e 

instalados corretamente com selos de vedação ou selante Loctite adicionados para as linhas do 

sensor, elementos de supressão e prensa-cabos. 

 

 

   

Cuidado 

Cuidados especiais devem ser tomados para evitar o acúmulo de carga eletrostática no 

equipamento devido ao repetitivo processo de carregamento, por exemplo, fluído de líquidos em 

alta velocidade, pós ou partículas de plásticos transportados pelo ar e outras cargas eletrostáticas 

para a superfície 

 

7501QB01 

LERBAKKEN 10, 8410 RØNDE DENMARK.       WWW.PRELECTRONICS.COM 

 

 

   

Revision date: 

2015-09-16 

 

      Version Revision 
               V2R0 

 

 

Page: 

6/6 

 

 

 

Instalação tb, Ex d: 

 

Entradas de cabos não utilizadas devem ser seladas pelo INMETRO, de acordo com a aprovação de 

elementos de supressão adequados para a aplicação e instalados corretamente. 

 

Apenas o certificado de cabos e prensa-cabos do INMETRO para Ex d / tb deve ser usado, que são 

adequados para a aplicação e instalados corretamente. 

 

O Sensor / Sonda aplicado deve ser adequado para a aplicação, instalado corretamente, e deve ser 

certificado pelo INMETRO. 

 

Se o transmissor estiver fisicamente conectado a uma possível fonte de calor ou resfriamento, por exemplo, 

através da montagem de um tubo de processo ou sensor de temperatura, a temperatura no ponto de 

conexão deve estar entre a faixa de temperatura ambiente dada no certificado. O sensor deve ser adequado 

para ser usado como entrada de equipamento no equipamento Ex d e nenhum volume deve ser adicionado 

no enclosure do 7501. 

 

O grau de proteção do IP 54 de acordo com a IEC 60529 é alcançado se o certificado Ex de prensa-cabos 

ou dispositivos de entrada de conduíte são usados e adequados para a aplicação e instalados 

corretamente. 

 

O grau de proteção do IP 68 de acordo com a IEC 60529 é apenas alcançado se o certificado Ex de prensa-

cabos ou dispositivos de entrada de conduíte são usados e adequados para aplicação e instalados 

corretamente com selos de vedação ou selante Loctite adicionados para as linhas do sensor, elementos de 

supressão e prensa-cabos. 

 

A tampa do display deve ser parafusada em todos os pontos e o fecho de segurança deve ser ajustado 

antes de colocá-lo em serviço. Não abra a tampa do display até 30 minutos depois de desconectar a 

alimentação a fim de permitir que os capacitores internos descarreguem, ou não abra a tampa do display a 

menos que a área seja conhecida como segura. 

 

Para uma temperatura ambiente que excede 70 ºC, cabos resistentes a aquecimento e prensa-cabos 

adequados para pelo menos 90 ºC devem ser usados. 

 

   

  O equipamento deve ser conectado em uma linha potencial correspondente. 

 

  Quando a faixa de temperatura do processo excede a faixa de temperatura de serviço ela deve ser 

verificada através de medições de temperatura no local, levando a pior condição em conta, que a 

temperatura de serviço não exceda a faixa do módulo. 

   

  Cuidado 

  Cuidados especiais devem ser tomados para evitar o acúmulo de carga eletrostática no equipamento devido 

ao repetitivo processo de carregamento, por exemplo, fluído de líquidos em alta velocidade, pós ou 

partículas de plásticos transportados pelo ar e outras cargas eletrostáticas para a superfície. 

 

  Nenhuma modificação no equipamento pelo cliente é permitida exceto o que é mencionado no manual ou no 

desenho de instalação. 

 