7501QI01 

LERBAKKEN 10, 8410 RØNDE DENMARK.       WWW.PRELECTRONICS.COM 

 

 

   

Revision date: 

2015-09-16 

 

      Version Revision 
               V2R0 

 

 

Page: 

2/6 

 

 

 

  

Ex ia

 

installation  

 

   

General installation instructions 

The sensor circuit is not infallibly galvanic isolated from the supply output circuit. However, the 

galvanic isolation between the circuits is capable of withstanding a test voltage of 500Vac during 1 

minute. 

 

The enclosure must be connected to the potential matching line. 

 

If the transmitter is physically connected to a possible source of heating or cooling, e.g. by 

mounting to a process pipe or a temperature sensor, the temperature at the point of connection 

shall be within the ambient temperature range as given in the certificate or in this manual. 

 

  

 Cable entries and blanking elements shall be used that are suitable for the application and correctly 

installed. 

 

 

 For installalation in zone 0 / EPL Ga, the transmitter must be installed such, that even in the event 

of rare incidents, ignition sources due to impact and friction, sparks are excluded. 

 

 Protection degree of IP 54 according to IEC 60529 is achieved if certified cable glands or conduit 

entry devices are used that are suitable for the application and correctly installed. 

 

 Protection degree of IP 68 according to IEC 60529 is only achieved if certified cable glands or 

conduit entry devices are used that are suitable for the application and correctly installed with 

sealing washers or Loctite sealant added to the threads of the sensor, blanking elements and cable 

glands. 

 

For group III (dust), electrostatic charging of the paint layer shall be avoided. 

 

 

 

 

 

 

7501QI01 

LERBAKKEN 10, 8410 RØNDE DENMARK.       WWW.PRELECTRONICS.COM 

 

 

   

Revision date: 

2015-09-16 

 

      Version Revision 
               V2R0 

 

 

Page: 

3/6 

 

 

 

Ex nA, ic installation:

 

 

 

 Certificate          IECEx DEK 15.0039 X  

 

Marking   

Ex nA IIC T6…T4 Gc 

 

 

Ex ic IIC T6…T4 Gc 

 

 

Ex ic IIIC T100°C Dc 

 

   

 

 

 

 

Standards:  IEC 60079-0: 2011, IEC 60079-11: 2011, IEC 60079-15: 2010 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sensor 

Terminal: 3,4,5,6 

Ex ic 

Uo: 9.6 VDC 

Io:   28 mA 

Po:  67 mW 

Lo:  45 mH 

Co:  28 μF 

Supply 

Terminal: 1,2 

Ex ic 

Ui: 35 VDC 

Li:  0 μH 

Ci:  2 nF 

Supply 

Terminal: 1,2 

Ex nA 

Umax : 35 VDC 

 

1

2

6

5

4

3

+

-

Supply

7501

Hazardous area 

Zone  2, 22 

Non Hazardous Area 

Type of protection Ex nA 

 

O-ring Sealing : Silicone 

T4: -40 ≤ Ta ≤ 85ºC  T4  (7501A ) 

T4: -40 ≤ Ta ≤ 80ºC  T4  (7501B ) 

T6: -40 ≤ Ta ≤ 60ºC  T6 

 

O-ring Sealing : FKM 

T4: -20 ≤ Ta ≤ 85ºC   (7501A ) 

T4: -20 ≤ Ta ≤ 80ºC   (7501B ) 

T6: -20 ≤ Ta ≤ 60ºC   

Type of protection Ex ic 

 

T4:  -40 ≤ Ta ≤ 85ºC  T100ºC (7501A ) 

T4;  -40 ≤ Ta ≤ 80ºC  T100ºC (7501B ) 

T6:  -40 ≤ Ta ≤ 60ºC  T85 ºC  

 

 

7501QI01 

LERBAKKEN 10, 8410 RØNDE DENMARK.       WWW.PRELECTRONICS.COM 

 

 

   

Revision date: 

2015-09-16 

 

      Version Revision 
               V2R0 

 

 

Page: 

1/6 

 

 

 

7501 IECEx Installation 

  

 

 

For safe installation of 7501 the following must be observed. The module shall only be installed by 

qualified personnel who are familiar with the national and international laws, directives and 

standards (IEC60079-14) that apply to this area.  

Year of manufacture can be taken from the first two digits in the serial number. 

 

Ex ia installation:

 

 

 

 Certificate          IECEx DEK 15.0039 X  

 

Marking 

 

 

 

   

 

 

 

 

 

Standards: 

IEC 60079-0: 2011, IEC 60079-11: 2011, IEC 60079-26: 2007 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hazardous area 

Zone 0, 1, 2, 20, 21, 22, Mines  

Non Hazardous Area 

T4:  -40 ≤ Ta ≤ 85ºC T100 ºC ( 7501A) 

T4:  -40 ≤ Ta ≤ 80ºC T100 ºC ( 7501B) 

T5:  -40 ≤ Ta ≤ 60ºC  T75 ºC   

T6:  -40 ≤ Ta ≤ 45ºC  T60 ºC 

Ex ia IIC T6...T4 Ga 

Ex ia IIIC T100°C Da 

Ex ia I Ma   (7501B ) 

Sensor 

Terminal: 3,4,5,6 

Uo: 9.6 VDC 

Io:   28 mA 

Po:  67 mW 

Lo:  35 mH 

Co:  3.5 μF 

Supply 

Terminal: 1,2 

Ui: 30 VDC 

Ii:   120 mA 

Pi:  0.84 W 

Li:  0 μH 

Ci:  2 nF 

1

2

6

5

4

3

+

-

Barrier

7501

 

7501QI01 

LERBAKKEN 10, 8410 RØNDE DENMARK.       WWW.PRELECTRONICS.COM 

 

 

   

Revision date: 

2015-09-16 

 

      Version Revision 
               V2R0 

 

 

Page: 

5/6 

 

 

 

Ex d, tb installation:

 

 

Certificate        IEC DEK 15.0039 X  

 

Marking 

 

 

 

   

 

Standards:IEC 60079-0: 2011, IEC 60079-1: 2007, IEC 60079-31: 2013 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Non Hazardous Area 

Hazardous area 

Zone  1, 2, 21, 22 

Ex d IIC T6…T4 Gb 

Ex tb IIIC T100°C Db 

Terminal: 3,4,5,6 

Sensor: RTD or TC

 

Terminal: 1,2 

Umax:   35 VDC 

 

Type of protection Ex tb 

 

O-ring Sealing : Silicone 

-40 ≤ Ta ≤ 85ºC  T100°C  (7501A ) 

-40 ≤ Ta ≤ 80ºC  T100°C  (7501B ) 

-40 ≤ Ta ≤ 70ºC  T85°C 

 

O-ring Sealing : FKM 

-20 ≤ Ta ≤ 85ºC  T100°C  (7501A ) 

-20 ≤ Ta ≤ 80ºC  T100°C  (7501B ) 

-20 ≤ Ta ≤ 70ºC  T85°C 

1

2

6

5

4

3

+

-

Supply

7501

 

Type of protection Ex d 

 

T4,T5:  -40 ≤ Ta ≤ 85ºC  (7501A ) 

T4,T5:  -40 ≤ Ta ≤ 80ºC  (7501B ) 

T6:       -40 ≤ Ta ≤ 70ºC   

 

 

7501QI01 

LERBAKKEN 10, 8410 RØNDE DENMARK.       WWW.PRELECTRONICS.COM 

 

 

   

Revision date: 

2015-09-16 

 

      Version Revision 
               V2R0 

 

 

Page: 

4/6 

 

 

 

Ex nA, ic installation: 

  

For an ambient temperature exceeding 70°C, heat resistant cables and cable glands suitable for at 

least 90°C shall be used. 

 

 If the transmitter is physically connected to a possible source of heating or cooling, e.g. by 

mounting to a process pipe or a temperature sensor, the temperature at the point of connection 

shall be within the ambient temperature range as given in the certificate. 

 

  

Cable entries and blanking elements shall be used that are suitable for the application and correctly 

installed.  

 

The enclosure must be connected to the potential matching line 

  

Applied screw terminal torque is max 0.4 Nm on all terminals. 

 

 

Protection degree of IP 54 according to EN 60529 is achieved if certified cable glands or conduit 

entry devices are used that are suitable for the application and correctly installed. 

 

Protection degree of IP 68 according to EN 60529 is only achieved if certified cable glands or 

conduit entry devices are used that are suitable for the application and correctly installed with 

sealing washers or Loctite sealant added to the threads of the sensor, blanking elements and cable 

glands. 

 

      For group III (dust), electrostatic charging of the paint layer shall be avoided

 

 

7501QI01 

LERBAKKEN 10, 8410 RØNDE DENMARK.       WWW.PRELECTRONICS.COM 

 

 

   

Revision date: 

2015-09-16 

 

      Version Revision 
               V2R0 

 

 

Page: 

6/6 

 

 

 

 Ex d, tb installation 

 

Unused cable entries must be sealed by the blanking elements supplied with the 7501 or other Ex d and/or 

Ex tb certified blanking elements suitable for the application. 

 

Only Ex d and/or Ex tb certified cable and cable glands shall be used that are suitable for the application and 

correctly installed. 

 

Protection degree of IP 54 according to IEC 60529 is achieved if Ex d certified cable glands or conduit entry 

devices are used that are suitable for the application and correctly installed. 

 

Protection degree of IP 68 according to IEC 60529 is only achieved if Ex d certified cable glands or conduit 

entry devices are used that are suitable for the application and correctly installed with sealing washers or 

Loctite sealant added to the threads of the sensor, blanking elements and cable glands. 

 

The display cover must be screwed all the way in and the safety catch must be fastened before putting into 

service. Do not open display cover until 30 minutes after disconnecting power to the equipment allowing 

internal capacitors to discharge, or do not open display cover unless area is known to be safe 

 

For an ambient temperature exceeding 70 °C, heat resistant cables and cable glands suitable for at least 

90°C shall be used. 

 

If the transmitter is physically connected to a possible source of heating or cooling, e.g. by mounting to a 

process pipe or a temperature sensor, the temperature at the point of connection shall be within the ambient 

temperature range as given in the certificate. The sensor shall be suitable for use as entry device on an Ex d 

enclosure and shall not add volume to the 7501 enclosure. The thread of the sensor must be in compliance 

with EN60079-1 / EN60079-31. 

 

  The enclosure must be connected to the potential matching line. 

 

When the process temperature range exceeds the service temperature range it shall be verified by on-site 

temperature measurements, taking the worst case conditions into account, that the service temperature does 

not exceed the range of the module.  

 

  For group III (dust), electrostatic charging of the paint layer shall be avoided 

    

  No modification to the enclosure is allowed by the customer except as mentioned in the manual or 

installation drawing. 

 

 

7501QF01 

LERBAKKEN 10, 8410 RØNDE DENMARK.       WWW.PRELECTRONICS.COM 

 

 

   

Revision date: 

2015-07-28 

 

      Version Revision 
               V1R0 

 

 

Page: 

2/5 

 

 

 

The entity concept 

The Transmitter must be installed according to National Electrical Code (ANSI-NFPA 70) and shall be 

installed with the enclosure, mounting, and spacing segregation requirement of the ultimate application.  

 
Equipment that is FM-approved for intrinsic safety may be connected to barriers based on the ENTITY 

CONCEPT. This concept permits interconnection of approved transmitters, meters and other devices in 

combinations which have not been specifically examined by FM, provided that the agency's criteria are 

met. The combination is then intrinsically safe, if the entity concept is acceptable to the authority having 

jurisdiction over the installation. 
The entity concept criteria are as follows: 

 

     The intrinsically safe devices, other than barriers, must not be a source of power. 

The maximum voltage Ui(V

MAX

) and current Ii(I

MAX

), and maximum power Pi(Pmax), which the device can 

receive and remain intrinsically safe, must be equal to or greater than the voltage (Uo or V

OC

 or V

t

) and 

current (Io or I

SC

 or I

t

) and the power Po which can be delivered by the barrier. 

 

The sum of the maximum unprotected capacitance (C

i

) for each intrinsically device and the interconnect-

ing wiring must be less than the capacitance (C

a

) which can be safely connected to the barrier. 

 

The sum of the maximum unprotected inductance (L

i

) for each intrinsically device and the interconnecting 

wiring must be less than the inductance (L

a

) which can be safely connected to the barrier. 

 

The entity parameters Uo,V

OC

 or V

t

 and Io,I

SC

 or I

t

, and C

a

 and L

a

 for barriers are provided by the barrier 

manufacturer. 

 

For Class II and Class III installations where rigid conduit is not used, seal cable entries against dust and 

fibres using a NRTL listed cable gland fitting. 

 

 

 

7501QF01 

LERBAKKEN 10, 8410 RØNDE DENMARK.       WWW.PRELECTRONICS.COM 

 

 

   

Revision date: 

2015-07-28 

 

      Version Revision 
               V1R0 

 

 

Page: 

1/5 

 

 

 

FM Installation drawing 7501 

 

For safe installation of 7501 the following must be observed. The module shall only be installed by 

qualified personnel who are familiar with the national and international laws, directives and 

standards that apply to this area.  

 

 

 Intrinsic safe installation:

 

 

 

Hazardous  classified Location 

Class I,II,II Division1 Groups, ABCDEFG 

Class I, Zone 0, IIC, Zone 20 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T4:  -40 ≤ Ta ≤ 85ºC   

T5:  -40 ≤ Ta ≤ 60ºC   

T6:  -40 ≤ Ta ≤ 40ºC 

   

Zone 20 Temperature Class: 

-40 ≤ Ta ≤ 85ºC  T100 ºC 

-40 ≤ Ta ≤ 60ºC  T75 ºC 

-40 ≤ Ta ≤ 40ºC  T60 ºC 

Non classified Location 

Terminal: 3,4,5,6 

Uo: 9.6 VDC 

Io:   28 mA 

Po:  67 mW 

Lo:  35 mH 

Co:  3.5 μF 

Terminal: 1,2 

Ui: 30 VDC 

Ii:   120 mA 

Pi:  0.84 W 

Li:  0 μH 

Ci: 2 nF 

UM < 250V 

Voc or Uo  < Vmax or Ui 

Isc or Io   <   Imax or Ii 

Po  <  Pi 

Ca or Co > Ci + Ccable 

La or Lo  > Li + Lcable 

 

 

The barrier must not 

be connected to any 

associated apparatus 

which uses or 

generates more than 

250 VRMS 

1

2

6

5

4

3

+

-

Barrier

7501

 

7501QF01 

LERBAKKEN 10, 8410 RØNDE DENMARK.       WWW.PRELECTRONICS.COM 

 

 

   

Revision date: 

2015-07-28 

 

      Version Revision 
               V1R0 

 

 

Page: 

3/5 

 

 

 

  

 

 

 Non Incendive installation:

 

 

 

Hazardous  classified Location 

Class I,II,III ,Division 2, Groups, ABCDFG 

Class I, Zone 2, IIC 

 

 

 

 

 

 

  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Non classified Location 

Terminal: 1,2 

Vmax: 35 VDC 

 

1

2

6

5

4

3

+

-

7501

Vmax 

35V

T4:  -40 ≤ Ta ≤ 85ºC  

T6:  -40 ≤ Ta ≤ 60ºC  

 

Terminal: 3,4,5,6 

Sensor: RTD or TC

 

O-ring Sealings   

Silicone rubber:-40°C ≤Ta ≤ +85°C 

FKM rubber:    -20°C ≤Ta ≤ +85°C 

 

Protection: Indoor and Outdoor TYPE 4X or IP66 