6
User Manual
Zenex Pro
Parameter Description
Settings
OP2 Function : Blower / Compressor Control
Positive (+) offset to Control Setpoint (SP) for defining Blower /
Compressor Setpoint.
BLOWER / COMPRESSOR SETPOINT
0 to 250
or
0.0 to 25.0
Parameter Description
Settings
OP3 Function : Alarm-2
Process High / Process Low Alarm-2 Setpoint.
ALARM-2 SETPOINT
Min. to Max.
Range for the
Input Type
Positive (+) or Negative (-) Alarm-2 deviation band.
ALARM-2 DEVIATION BAND
-199 to 999
or
-199.9 to 999.9
Symmetrical Alarm-2 window band.
ALARM-2 WINDOW BAND
3 to 999
or
0.3 to 999.9
OP3 Function : Auxiliary Control
Parameter Description
Settings
Positive (+) or Negative (-) offset to Control Setpoint (SP) for
defining Auxiliary Setpoint.
AUXILIARY CONTROL SETPOINT
(Min. Range - SP)
to
(Max. Range - SP)
for selected Input
OP2 Function : Auxiliary Control
Parameter Description
Settings
Positive (+) or Negative (-) offset to Control Setpoint (SP) for
defining Auxiliary Setpoint.
AUXILIARY CONTROL SETPOINT
(Min. Range - SP)
to
(Max. Range - SP)
for selected Input