The following examples illustrate appropriate parameter value selections.
Example 1
: Pressure Transmitter producing
for
4 to 20 mA
0 to 5 psi
Example 2
: Relative Humidity Transmitter producing
for
1 to 4.5 V
5 to 95 %RH
Example 3
: Temperature Transmitter producing
for
0 to 20 mA
-50 to 250 °C
Presume the Temperature is to be measured
with 0.1 Resolution, that is -50.0 to 250.0°C.
Input Type
: 0-20 mA
Signal Low
: 0.00 mA
Signal High
: 20.00 mA
PV Resolution : 0.1
Range Low
: -50.0
Range High
: 250.0
X (mA)
Y (psi)
4.00
20.00
Signal Low
Signal High
0.00
Range Low
5.00
Range High
Presume the pressure is to be measured
with 0.01 Resolution, that is 0.00 to 5.00 psi.
Input Type
: 4-20 mA
Signal Low
: 4.00 mA
Signal High
: 20.00 mA
PV Resolution : 0.01
Range Low
: 0.00
Range High
: 5.00
X (V)
Y (% RH)
0
5
Signal Low
Signal High
0
95.0
1.000
4.500
5.0
Range Low
Range High
Presume the humidity is to be measured
with 0.1 Resolution, that is 0.0 to 100.0 %.
Input Type
: 0-5 V
Signal Low
: 1.000 V
Signal High
: 4.500 V
PV Resolution : 0.1
Range Low
: 5.0
Range High
: 95.0
X (mA)
Y (°C)
Signal Low
Signal High
250.0
0.00
20.00
-50.0
Range Low
Range High