40
OUTPUT-1
(Terminals 4, 5 & 6)
The Output-1 can be configured (through jumper settings) as either Relay, SSR Drive or DC Linear output. Note that either
Current (mA) or Voltage is provided as DC Linear output.
Figure 2.3 (c )
6
5
4
Output-1: mA / V
Figure 2.3 (a)
6
5
4
NO
C
Output-1 : Relay
NC
Output-1: SSR
6
5
4
Figure 2.3 (b)
Relay Output
Potential-free Relay changeover contacts NO (Normally Open), C (Common) & NC (Normally Closed) rated 10A/240 VAC
(resistive load) are provided as Relay output as shown in Figure 2.3 (a).
SSR Output
Connect (+) and (-) terminals of SSR to terminals 6 & 5, respectively as shown in Figure 2.3 (b). Use Zero-Crossover, 3 to 30
VDC operated SSR.
DC Linear Current/Voltage (mA / V) Output
The DC Linear Current (0/4-20mA) or Voltage (0-5/10V) output is also available at Terminal 6 (+) and Terminal 5 (-) as shown in
Figure 2.3 (c) if the Output-1 is configured for DC Linear.
Figure 2.4 (a)
Relay Output
NO
C
NC
9 (16)
7 (18)
8 (17)
SSR Output
Figure 2.4 (b)
9 (18)
7 (16)
8 (17)
9
7
8
Figure 2.4 (c)
DC Linear
mV/V/mA
OUTPUT- 2
(Terminals 7, 8 & 9)
The Output-2 is fitted as either Relay/SSR or DC Linear module.
In case of Relay/SSR; the Output-2 is jumper selectable as either Relay or SSR as shown in Figure 2.4(a) & 2.4(b)
respectively.
In case of DC Linear; Output-2 is supplied as either DC Current or DC Voltage. Connections are shown in figure 2.4(c).
OUTPUT- 3
(Terminal 16, 17 & 18)
The Output-3 module (if fitted) can be configured as either Relay or SSR through hardware jumper setting as shown in Figure
2.4(a) & 2.4(b) respectively.
POWER SUPPLY
The controller accepts single phase, 50/60 Hz Line Voltage ranging from 85 VAC to 264 VAC. Use
well-insulated copper conductor wire of the size not smaller than 0.5mm for power supply
2
connections. Connect Line Voltage as shown in Figure 2.5.
Figure 2.5
13
12
L
N
User Manual
EPSILON 96X96