Parameter Description
Settings
(Default Value)
‘POWER FAIL RECOVERY’ STRATEGY
Abort
A running profile shall terminate in case of power failure.
Continue
(a) If a ramp segment was in progress at the time of power failure
then the ramp segment execution resumes with the profile
setpoint prevailing at the time of power failure.
(b) If a soak segment was in progress at the time of power failure
then the soak segment execution resumes with the balance time.
OUTPUT OFF
Set to ‘Yes’ if after the end of profile, all the control outputs are to be
forced Off
till the issuance of next profile Start command.
No
Yes
(Default : No)
TARGET SETPOINT
Set the Target (End) value for the selected profile segment
number.
(Available only holdback type in other than None).
Set the band value (deviation from profile setpoint) for the profile
holdback feature.
HOLDBACK VALUE
Disable the Holdback Band or set the scope (up, down or both) for
the profile holdback feature.
HOLDBACK TYPE
SEGMENT NUMBER
Select profile segment number for which the Target Setpoint/Time
Interval values are to be edited.
(Default : -199)
Min. to Max. Range
specified for the
selected Input Type
None
Down
Both
Up
(Default : None)
Parameter Description
Settings
(Default Value)
Table 8.2
Profile Setting Parameters : PAGE 14
0 to 9999 Minutes
(Default : 0)
1 to 999
(Default : 1)
1 to n
(n = 4, 8, 12 or 16 depending
on factory configuration)
(Default : 1)
User Manual
EPSILON
Set the time duration of ramping or soaking for the selected profile
segment number.
TIME INTERVAL