10
4. Press and release the REC button;
5. CMD button to enable feature, or GRV + button to disable feature.
6. Finally, remove PROG jumper
eliMinate BraKe inertia tiMe
Time in which the brake will eliminate the inertia of the gate due to its displacement
velocity before entering the ramp region to reduce speed.
Values:
20 adjustment levels.
0 = 10.0 msec.
1 = 12,0 msec.
2 = 14.0 msec.
...
19 = 48.0 sec.
Operation:
1. Gate must be stopped;
2. Close jumper PROG;
3. Press and release the button CMD (14x) to enter the function;
4. Press and release the REC button;
5. CMD button to decrement value, or REC to increase value.
6. Finally, remove PROG jumper.
autoMatiC Closing (pause)
Semiautomatic Mode (Jumper A / S = Closed)
After complete gate opening cycle, a new command for the closing cycle is
required.
Automatic Mode (Jumper A / S = Open)
After a complete of the gate opening cycle, the programmed PAUSE time will be
decremented every second, and when zero, the closing cycle will start.
Clockwise = shorten time. (Minimum = 1sec)
Counter-clockwise = increase time. (Maximum = 4min)