TC310VP Instruction Manual

Powtier Controls Limited

TECHNICAL SPECIFICATION

INPUT
Thermocouple Standard

ASTM E230, BS4937, DIN 43710.

Cold junction compensation

Automatic.

Thermocouple break protection

Upscale fitted as standard, display shows "bbb." (b:blank)
Downscale fitted as an option.

Resistance Thermometer 2 or 3 wire

Any lead resistance error is automatically reduced by
using 3 wires.

RTD (Pt 100)

BS 1904, DIN 43760.

VALVE POSITION OUTPUT
Motor supply voltage

24Vac to 240Vac (EXTERNAL STEP DOWN
TRANSFORMER REQUIRED).

Output twin triacs rating

2Arms, 24Vac to 240Vac.

Feedback potentiometer

100 to 1000 Ohms.

CONTROL
PID control

Proportional, Integral and Derivative.

  Proportional band Xp

2.5% to 15% of span.

  Integral time ti

Switching integral time 5 to 40 minutes.

  Derivative time

td Switching derivative time 0.5 to 5 minutes.

PD control (option)

Proportional and derivative.

  Proportional band Xp

2.5% to 15% of span.

  Derivative time td

0.5 to 5 minutes.

  Manual reset

PD control only, 0 to 50% output power at span.

ON/OFF control (option)

Hysteretic 0.5% of span.

ALARMS OUTPUTS (option)
Relay

Normally energised and de-energised in alarm
conditions. 2A resistive at 230Vrms.

Alarm LED

Flashing LED at fascia.

Low deviation

Adju0.5% to -8% of span.

High deviation

Adjustable -0.5% to +8% of span.

Band deviation

Adjustable 1.5% to 8% of span.

RETRANSMISSION SIGNAL (option)
Analogue signal

5V, 5mA max.m signal linear to span.

ENVIRONMENTAL
Supply voltage

115/230V +/-15% 50/60Hz
100/200V +10% -15% 50/60Hz.

Operating temperature

0 to 50 °C.

Storage temperature

-20 to +80 °C.

PERFORMANCE
Indication accuracy

Better than 0.5% of span +/-1 digit.

Supply voltage variation

Negligible effect within operating range.

GENERAL
Display digit

3 digit 7 segment with negative sign display;
digit size 13mm height by 7.4mm width.

Error indication

9 LED display bar; central LED +/- 0.4% of span
+/-1 degree and +/-0.8% of span +/-1 degree
per LED above and below setpoint.

Dimensions

96x96x190mm.

Weight

2Kg maximum.

Power consumption

6VA maximum.

14 March 1995

- 7 -

310VPIM

Issue 2.0

Содержание Tactical 310

Страница 1: ...OLLER WITH VALVE POSITIONER OUTPUT INSTRUCTION MANUAL CONTENTS DESCRIPTION 2 INSTALLATION 2 CONNECTIONS 3 CONTROL ADJUSTMENTS 4 TUNING 5 ALARM SETTING 6 TECHNICAL SPECIFICATION 7 ORDERING INFORMATION...

Страница 2: ...etpoint changeover switch on the front panel Setpoint adjustment is made by turning the setpoint thumbwheel which is concealed behind the door on the front panel Wiring connections are made at the bac...

Страница 3: ...TC310VP Instruction Manual Powtier Controls Limited CONNECTIONS Typical TC310VP wiring Schematic Terminal connection diagram 14 March 1995 3 310VPIM Issue 2 0...

Страница 4: ...nual Reset optional can be used to remove the steady state error inherent in PD control P10 Not used P11 Not used P12 High Low Band Alarm optional only one type on any instrument can be used to give a...

Страница 5: ...to table 2 8 Progressively reset P13 P14 as far clockwise as possible without the introduction of system hunting Table 1 Switch settings for integral and derivative time constant SID ti td SID ti td 1...

Страница 6: ...just comes on The high alarm will now operate at t degrees above any chosen set point temperature 2 STEPS IN SETTING A LOW ALARM LEVEL 2 1 Ensure that the sensor input to the controller is at a steady...

Страница 7: ...span Derivative time td 0 5 to 5 minutes Manual reset PD control only 0 to 50 output power at span ON OFF control option Hysteretic 0 5 of span ALARMS OUTPUTS option Relay Normally energised and de en...

Страница 8: ...r 49 OPTIONS No option 01 Low deviation alarm 21 High deviation alarm 22 Band deviation alarm 23 Two term PD Control 31 On off control 32 Downscale Thermocouple break protection 61 Retransmission sign...

Отзывы: