Vision Mini
User Instructions Doc Ref M608 issue 1.0 June 2021.
Positioning
– fasten the unit to the upper part of the metallic support
– verify the correct hooking to the interlocking points
To facilitate connections, a spacer can be used to keep the
bottom of the unit away from the wall.
2.11 Condensation drain preparation
This appliance is complete with a tray for collecting the
condensation produced during operation, which must be
channelled to a suitable place for drainage.
The size and positioning of the drainage tube are shown
below.
Preliminary warnings
If the line flows into a container (e.g. a tank), do not close
the container hermetically and avoid immersing the
draining pipe into the water.
The hole for the condensation pipe must always slope
towards the outside.
The exact position in which to place the pipe mouth is
indicated on the template.
Check that the expelled water does not cause any damage
or problems to people or objects. During winter, this water
may create sheets of ice outside.
When connecting the condensation drain, be careful not
to squeeze the rubber duct.
It is possible to empty the collection tray using the safety
drain at the base of the appliance if necessary.
If you do not want to prepare an external drainage pipe in
"cold only" mode, it is advisable to close the condensate
drain with a plug.