Vision Mini
User Instructions Doc Ref M608 issue 1.0 June 2021.
Avoid placing the unit within 1 metre of radio and video
equipment.
Do not install over heat sources.
Make sure that:
• the installation site of the unit must be chosen with the
utmost care to guarantee adequate protection from
shocks and consequent damage
• the wall is able to support the weight of the appliance
• the wall section does not feature building supporting
elements, pipes or power lines
• there are no obstacles to the free circulation of air through
the holes (plants, leaves...)
• the appliance must be installed in a position where it can
be easily serviced
• the safety distances between the units and other
appliances or structures are scrupulously respected so
that the air entering and leaving the fans is free to circulate
If the appliance is installed incompletely or on an
inappropriate base, it could cause damage to persons or
property if it should detach from its base.
The unit should not be installed in a position where the air
flow is aimed directly at the people nearby.
Provide the following:
• a nearby drain for the outflow of condensate
• a compliant power supply nearby
• fixing elements suitable for the type of support
Specific warnings for R290
The installation of the unit does not have any special
requirements (such as minimum area, room ventilation
requirements or sensors) in relation to the use of
refrigerants as the quantity used is less than 149 gr.
2.9 Installation minimum distances
The clearance zones for the installation and maintenance of
the appliance are shown in the figure. Established spaces are
necessary to avoid barriers to airflow and allow for normal
cleaning and maintenance.
Make sure that there is sufficient space to allow the
panels to be removed for routine and supplementary
maintenance operations.
A
High wall installation
B
Low wall installation
200
2500 max.
60
A
60
B
50
2000
2.10 Positioning
The units can be wall-mounted upwards or downwards.