Powrmatic OUH series Скачать руководство пользователя страница 8

3. General Requirements

3.1 Related Documents

Installation of air heaters must be in accordance with the relevant 

requirements of:

BS  5410:  Part  2:  1978  Code  of  Practice  for  Oil  Firing 

Installations of 45kW and Above

The Building Regulations

The I.E.E. Regulations

It should also be in accordance with relevant requirements of 

the local authority and fire authority, in addition the following 

British Standard Codes of Practice must be observed

CP.3  Ch  IV  Precautions Against  Fire    Part  2  Shops  and 

Departmental Stores  Part 3 Office Buildings,

and the relevant publications of OFTEC.

3.2 Location

The location chosen for the air heater must permit the provision 

of a satisfactory flue system and an adequate air supply. The 

location must also facilitate ease of servicing and satisfactory 

air circulation around the heater.

The air heater must be installed strictly in accordance with any 

fire  regulations  or  insurance  company's  requirements 

appertaining to the area in which the heater is located, particularly 

where special risks are involved such as areas where petrol 

vehicles are housed, cellulose spraying areas, and wood working 

departments etc.

The air heater must be installed either:

  (a) suspended by chains or straps of adequate strength to  

      safely carry the weight of the unit and ancillary equipment  

    or

  (b) On specifically designed cantilever  brackets from a non- 

    combustible wall or

  (c) On a level non-combustible surface which  is capable  

      of adequately supporting the  weight of the air heater and  

    any ancillary  equipment.

The heater must not be installed in conditions for which it is 

not specifically designed e.g. highly corrosive atmospheres, 

vitiated atmospheres, or where adverse wind conditions may 

be experienced. Where the location of the heater is such that it 

might suffer external mechanical damage e.g. from overhead 

cranes, fork lift trucks etc. it must be suitably protected.

Any ducting should be kept as short and direct as possible having 

regard to the distribution of the heated air.

Any combustible material adjacent to the heater and flue systems 

must be so placed as to ensure that its temperature does not 

exceed 65°C (150°F).

3.3 Oil Supply

3.3.1 Main Storage Tank and fittings

Construction and installation should be in accordance with:

(a) BS 5410 Part 2 Section 6

(b) BS 799 Part 5

(c) BS 1563 and BS1564

The latter three standards apply to cast iron sectional, mild steel 

sectional, and mild steel welded tanks respectively and therefore 

must be applied appropriately.

3.3.2 Service Tanks and fittings

3.3.2.1 Construction

These should be designed and constructed in accordance with 

BS 799 Part 5

3.3.2.2 Installation

The installation should be in accordance with:- BS 5410 Part 2. 

In addition the service tank installation must comply with local 

regulations and by-laws and with the requirements of insurance 

companies

3.3.3 One Pipe System (Storage to burner)

3.3.3.1 General

Refer  also  to  the  detail  provided  in  the  burner  handbook 

regarding 

pipe sizing. These must be generally in accordance with B S 

799 Part 3 and BS 5410 Part 2.

Particular attention is drawn to the following:

a) Pipe jointing compounds must be capable of withstanding 

the  solvent  action  of  the  fuel  oil  under  all  operating 

temperatures and pressures. Jointing compounds containing 

oil shall not be used. Hemp and other fibrous materials shall 

not be used as packing for screwed joints.

b) Soft solder copper tube fittings and galvanised pipes and 

fittings must not be used.

e) Oil lines must be completely air-tight.

d) The pump suction must not exceed a maximum of 0.4 bar 

(30cm Hg). Beyond this limit gas may be released from the 

oil.

3.3.3.2 Single Pipe System - Gravity Feed

Warning:

 The burners are supplied adjusted for  a single pipe 

system. If the burner is to be used on a twin pipe system the 

Internal bypass plug of the burner oil pump must be fitted. Refer 

to the burner instruction booklet.

Ideally the return pipe should terminate within the oil tank at 

the same level as the suction line, both being below the minimum 

oil level.

3.3.4 Fire Valve

It is recommended that the fire valves should be installed as 

follows:

1. Main storage to service tank supply (if applicable)

2. Main storage to burner supply

3. Service tank to burner supply (if applicable)

Fire valves should be installed generally in accordance with the 

requirements of BS 799: Part 5. The fire valve should be situated 

in an easily accessible position as near the tank as possible and 

where practicable within the boundary of the tank chamber or 

catchpit retaining wall.

3.4 Flue System

The flue system should generally be in accordance with 

BS 5410 Part 2.

Materials used for the flue system should be mechanically robust, 

resistant to internal and external corrosion, noncombustible and 

durable under the conditions to which they are likely to be 

subjected. Prevention of condensation within the flue should 

be an important factor in the design of the flue system. In order 

to minimise condensation the use of doublewalled flue pipe or 

insulation is recommended.

Where condensation in the flue is unavoidable, or rain ingress 

is possible, provision must be made for a condensate drain 

connected to a suitable drain or gully. The condensation pipe 

from the flue to the disposal point should be of non-corrodible 

material of not less than 22mm (¾ in) size.

Facilities should be provided for disconnecting the flue pipe 

from the air heater for inspection and servicing purposes. Bends 

with removable covers should be fitted for inspection and 

cleaning purposes where considered appropriate.

The flue should terminate in a freely exposed position and must 

be situated such that products of combustion do not enter any 

opening in a building in such concentration as to constitute a 

health hazard.

3.5 Air Supply

Where the air heater is to be installed in the space to be heated 

it requires the space containing it to have a permanent air vent 

direct  to  outside  air.  The  air  vent  should  have  negligible 

resistance and must not be sited in any position where it is likely 

to be easily blocked or flooded, neither should it be positioned 

adjacent to an extraction system carrying flammable vapour.

The  air  supply  requirement  that  follows  is  related  to  the 

maximum rated heat input of the heater, or heaters if more than 

one is installed in the same space.

4

Содержание OUH series

Страница 1: ...Users Installation and Servicing Instructions WARNING THIS APPLIANCE MUST BE EARTHED CE OUH Range Users Installation Servicing Instructions Issue 4 March 2010 The OUH Range...

Страница 2: ...s and local regulations 2 The appliance has been professionally commissioned 3 The appliance has been maintained on a yearly basis by a competent servicing company 4 The appliance has been used in acc...

Страница 3: ...5 minutes later the heater fan will automatically stop 4 1 Summer Winter Modes Certain types of external controls will provide for two modes of operation i e Summer The heater fan alone will run at th...

Страница 4: ...n of Heater 5 5 Air Distribution System 7 6 Commissioning Testing 7 7 Servicing 7 8 Wiring Diagram 9 9 Short List of Parts 9 Figure Title Page 1 Limit Thermostat 8 Table Title Page 1 Dimensions 3 2 Sp...

Страница 5: ...s The OUH F has an axial type fan assembly fitted at the rear of each heater to circulate the air being heated across the combined combustion chamber heat exchanger A centrifugal fan variation is pres...

Страница 6: ...0 F OUH20 C Rear View E F F D A K Side View B C M Front View Rear View L 50mm Side View J H G Front View OUH30 45 60 C OUH30 45 60 F Rear View E F D A K Side View B C M Front View Rear View 50mm L Sid...

Страница 7: ...l flue diameter THROW 8 5 16 1 25 3 34 1 N A N A N A N A Table 4 Burner Settings 35sec Oil Net CV Hi 42 69MJ kg Riello Burners Nozzle Pump Head Setting Combustion Nominal Model Type Make Size Angle Ty...

Страница 8: ...t 2 Particular attention is drawn to the following a Pipe jointing compounds must be capable of withstanding the solvent action of the fuel oil under all operating temperatures and pressures Jointing...

Страница 9: ...Rating Air Vent Area of Air Heaters Air direct from outside Up to 60kW 4 5 cm kW in excess of 7kW From 60kW up to 730kW 4 5 cm kW Where the air heater is to be installed in a plant room the heater re...

Страница 10: ...inal connection of the incoming mains supply and completion of the control circuit 230V via a room thermostat time clock etc All units must be earthed The electrical supply must be run to a point adja...

Страница 11: ...a Powrtrol or MC200 is being used that the Winter mode is selected 6 5 Lighting the Air Heater Refer also to the burner instruction booklet 1 Remove the burner cover after releasing the three retainin...

Страница 12: ...ur hexagon headed bolts that secure the fan to the rear panel 6 Reassemble in reverse order 7 5 2 Centrifugal Fan 1 Inspect the fan blades to see that they are not damaged and that there is no build u...

Страница 13: ...ue Brown Black Gr Yellow MAIN FAN CAPACITOR VENT VENT CLOCK O P HEAT IN HEAT OUT L N POWRTROL Additional Oil Valve 8 Wiring Diagram 9 Short List of Parts Only originally specified parts may be fitted...

Страница 14: ...rovement we reserve the right to alter specifications without prior notice HEATING DIVISION Hort Bridge Ilminster Somerset TA19 9PS Tel 01460 53535 Fax 01460 52341 BSI Registered Firm FM 414 Ind Comm...

Отзывы: