background image

page no. 10 of 12      

    

 CECx

   Users, Installation & Servicing Instructions  Doc Ref M503 issue 3.3 Jan 2020.

WARNING: Before undertaking any 

component replacement turn off and isolate 

the electrical supply.

1. Remove the two screws securing the electrical panel to 

the casing and hinge down panel.

2. Disconnect the incoming electrical connections and 

the earth lead. Release the locking nut of the cable gland 

on the top of the unit and withdraw the incoming supply 

cable.

3. Release the unit from its suspension points and lower 

to a safe working area.

4. Remove the four bolts securing the fan to the casing 

and lift out fan.

5. Remove terminal box cover from motor and disconnect 

motor wiring.

6. Check that replacement fan is of the correct type. 

7. Reassemble unit in reverse order and reinstall.

1. Pull off the thermostat cover, whilst pushing in the side 

retaining tabs with a small screwdriver, and disconnect 

electrical connections.

2. Remove the two screws securing the thermostat to the 

electrical panel.

3. Reassemble in reverse order.

Item

Description

Usage

Part No.

Main Air Fan

CECx1400
CECx2250
CECx3350
CECx4500
CECx6500

PM-6-400-B-15
PM-6-500-B-15
PM-6-550-B-15
140232006/E/15
140232007/E/15

Thermostat

All

143000534

CECx Fixing Kit

All

CECXFIX

Содержание CECx 1400

Страница 1: ...w w w p o w r m a t i c c o u k CECx User Installation Servicing Manual Issue 3 3 Jan 2020 Doc Ref M503 Issue 3 3 Jan 2020 ...

Страница 2: ...mentation As much detail as possible on the fault 3 Your supplier or installer will then contact Powrmatic to make a guarantee claim on your behalf Conditions of Guarantee 1 The destatification fan must have been installed by a competent recognised installer and in accordance with the manufacturer s instructions I E E regulations and local regulations 2 The destatification fan has been used in acc...

Страница 3: ...tion 1 1 Introduction 4 Dimensions 4 1 2 Technical data 5 1 3 General Requirements 5 Installation 2 1 Fitting the unit 6 2 2 Wiring Diagrams 8 2 3 Commissioning and Testing 9 2 4 Servicing 9 2 5 Replacement of Faulty Items 10 Additional Documents 3 1 Short List of Parts 10 Users Installation and Servicing Instructions CONTENTS Contents ...

Страница 4: ...s operated automatically by an inbuilt thermostat to turn on when the air temperature at high level exceeds the thermostat setting The Calecon unit will automatically recirculate the high level hot air in high roofed buildings drastically reducing stratification and heat losses and minimise the temperature gradient between low and high level The unit will turn off automatically when the air temper...

Страница 5: ...t 1 3 1 Location Calecon units will be effective in any high roofed building where temperature stratification will otherwise occur Units should be installed at the highest available location once the roof architecture and maximum mounting height for the unit have been taken into account see section 1 2 Units should be placed in positions where the downward directed airflow will not be impeded by r...

Страница 6: ...is adequate to take the weight of the particular destratification unit Once the destratification fan is in position the wiring can commence 2 1 1 1 CECx Fixing Kit The CECx fixing kit is a fast locking solution for quick and easy suspension of our CECx destratification fans Features Up to 6 times faster to install than traditional methods Key less no tool required for adjustment Ergonomic buttons ...

Страница 7: ...d are used for the electrical installation The length of the conductors between the cord anchorage and the terminals must be such that the current carrying conductors become taut before the earth conductor if the cable or cord slips out of the cord anchorage Any external controls that are used in conjunction with the units must be of an approved type To wire the Calecon unit 1 Remove the two screw...

Страница 8: ...Blue Brown MAINS SUPPLY 230V 1ph 50 Hz EARTH NEUTRAL LIVE CAPACITOR White Brown 1 CEWAL RQ10 THERMOSTAT 2 3 1 N L Gr Yellow Blue Brown MAINS SUPPLY 230V 1ph 50 Hz EARTH NEUTRAL LIVE Blue Brown Black Gr Yel 2 2 1 1ph Calecon CECx1400 2250 3350 REMCO Fans Blue Brow Black Gr Yel n CAPACITOR 2 2 Wiring Diagrams 2 2 2 1ph Calecon CECx4500 CECx6500 EBM Fans ...

Страница 9: ...can cause damage Set the thermostat to the required value normally 2 to 3 above the design temperature of the building The unit is now ready for operation WARNING Before undertaking any servicing turn off and isolate the electrical supply Use a safe means of access Note Units should be serviced at least annually Motors are sealed for life and do not require servicing 1 Remove the two screws securi...

Страница 10: ...he four bolts securing the fan to the casing and lift out fan 5 Remove terminal box cover from motor and disconnect motor wiring 6 Check that replacement fan is of the correct type 7 Reassemble unit in reverse order and reinstall 2 5 2 Thermostat 1 Pull off the thermostat cover whilst pushing in the side retaining tabs with a small screwdriver and disconnect electrical connections 2 Remove the two...

Страница 11: ...page no 11 of 24 CECx Users Installation Servicing Instructions Doc Ref M503 issue 3 3 Jan 2020 Notes ...

Страница 12: ...Dublin 24 tel 353 0 1452 1533 fax 353 0 1452 1764 e mail info powrmatic ie web www powrmatic ie Getting In Touch Powrmatic pursues a policy of continues improvement in both design and performance of its products and therefore reserves the right to change amend or vary specifications without notice Whilst the details contained herein are believed to be correct they do not form the basis of any cont...