Battery Runtime Charts
1
(in minutes)
Powerware 5125 2200 (P22)
Load in VA
Load in watts
Standard
1100
800
14
2200
1600
5
Dimensions WxDxH (mm) 205 x 493 x 250
Powerware 5125 1500i RM (P18)
Load in VA
Load in watts St1 EBM +2 EBM +3 EBM +4 EBM
750
670
13
57
161
171
205
1500
1340
5
23
49
73
96
Rack height (U)
-
2
4
6
8
10
Depth (mm)
-
467
467
467
467
467
Powerware 5115 750 VA (P08)
Load in VA
Load in watts
Standard
200
128
38
300
192
27
500
320
14
600
402
9
750
503
6
Dimensions WxDxH (mm) 150 x 335 x 193
Powerware 9125 1000 VA (P10)
Load in VA
Load in watts
St1 EBM
+2 EBM
200
140
37
271
546
400
280
19
142
278
700
490
9
72
156
850
595
6
59
124
1000
700
5
48
104
Tower width (mm)
–
89
178
267
Rack height (U)
–
2
4
6
Powerware 9125 1500 VA (P15)
Load in VA Load in watts
Standard
+1 EBM
+2 EBM
+3 EBM
+4 EBM
400
280
46
177
331
501
682
700
490
25
96
180
272
370
850
595
21
76
142
214
292
1000
700
16
61
115
174
237
1250
875
11
46
87
131
179
1500
1050
8
37
70
106
144
Tower width (mm)
–
89
178
267
356
445
Rack height (U)
–
2
4
6
8
10
Powerware 5125 Rackmount 3000 VA (P33)
Load in VA Load in watts
Standard
+1 EBM
+2 EBM
+3 EBM
+4 EBM
600
540
48
151
257
365
473
1500
1350
15
61
103
146
190
2400
2160
7
37
62
89
115
3000
2700
5
25
49
69
90
Rack height (U)
–
2
4
6
8
10
Depth (mm)
–
610
610
610
610
610
1. Battery runtimes are approximate and may vary with equipment,
configuration, disk access, battery age, temperature, etc. Note: EBM
part number information is located on page 1 of this data sheet.
Powerware 9125 6000 VA (P64)
Load in VA Load in watts
Standard
+1 EBM
+2 EBM
+3 EBM
+4 EBM
1400
37
107
186
271
361
2100
24
70
121
178
237
2800
19
49
85
125
167
3500
13
37
65
96
128
4200
10
30
52
76
102
Rack height (U)
-
5
8
11
14
17
Powerware 9125 3000 VA (P30)
Load in VA Load in watts
Standard
+1 EBM
+2 EBM
+3 EBM
+4 EBM
875
16
57
90
150
200
1050
13
55
72
120
160
1750
7
28
48
68
88
2100
5
25
38
54
70
Rack height (U)
-
2
4
6
8
10