background image

9910 pSeries UPS Technical Specifications

1

5115 = P07; 9125 = P10, P15 P30, P64; 5125 = P18, P22, P33

Electrical

Allowable input range

9125, 5115

120 or 208/240 Vac, model dependent

5125

Input power factor

9125

>.95 typical

5115, 5125 

.90 typical @ full load

Output wave form

All Models

Sine wave

Output regulation

5115, 5125, 

±5%

9125

±3%

Output voltage THD

5115, 5125, 9125 5%, linear load

Load crest ratio

9125

3:1

5115, 5125 

N/A

Battery

Battery type

All Models

Sealed, maintenance-free lead-acid

Recharge time

9125

2 hours to 80% capacity

5115, 5125

<3 hours to 90% capacity

Diagnostics

All Models

Automatic online test without exposing the 
load

General

Architecture

5115, 5125

Line-interactive

9125 

True online double-conversion

User interface

9125

8 LEDs indicating system status

5125 

5 LEDS indicating system status

5115

4 LEDs indicating system status

Diagnostics

All Models

Full system self-test on power up

UPS bypass

All Models

Automatic on overload or UPS failure

Replacement modules

5125 (P33)

Hot-swappable batteries and electronics

5115, 5125,

Hot-swappable batteries

9125

Communications

5125 (P33)

3 Serial ports

5115, 5125 

1 Serial port

(P18, P22), 9125

Networks

5125, 9125

Connectivity via Ethernet is an orderable 
option, FC 2934

5115

Connectivity via Ethernet (Thinwire or 
Twisted Pair) & Token Ring are orderable
options, FC 2103, 2203, 2303 

Safety

9125

UL, CSA, NOM

5115, 5125 

UL 1778, CSA-C22.2 No. 107.1; 
EN 50091-1, EN 60950

Environmental

Audible noise

5115, 5125

<45 dBA typical

9125 

<55 dBA typical

Ambient operating

5115, 9125 

0°C to 40°C (32°F to 104°F)

5125

10°C to 40°C (50°F to 104°F)

Relative humidity

9125

5 to 90% non-condensing

5115, 5125

5 to 95% non-condensing

EMC markings

5115, 5125 

FCC Class A

9125

FCC Class B and VCCI Class II

1. For additional specifications, see the Model Selection Guide. Due to continuing product improvement

programs, specifications are subject to change without notice.  

7029-6C3,

7026-6M1,

7026-6H1, 

UPS 7043-43P 7044-44P 7028-6E1  6E3

7025-6F0 7025-6F1 7028-6E4 

7028-6C1 

7028-6C4 7026-B80

7038-642

6H0

9112 

model

150

170, 270

p610

p615

p620

p620

p630

7046-B50

p610

p630

p640

p650

p660  265, 275

P07

x

x

x

x

P10

x

x

x

x

x

x

P15

x

x

x

x

x

x

x

x

P18

x

x

x

x

x

P22

x

x

x

x

x

x

x

P30

x

x

x

x

x

x

P33

x

x

x

x

x

P64

x

x

x

x

x

x

For 7046-671 (p670), 7040-681 (p690) and RS/6000 SP information, contact Powerware.

Choosing the right UPS for your pSeries and IntelliStation

Отзывы: