6.
SPECIFICATIONS
MODEL
PowerWalker VI 1000RT/LE
PowerWalker VI 1500RT/LE
Capacity
VA/W
1000VA/600W
1500VA/870W
Input
Voltage
220/230/240VAC
Acceptable
Voltage Range
0-300VAC
Nominal
Frequency
50/60Hz ±5Hz for Normal Mode; >40Hz for Generator Mode
Output
Voltage
220/230/240VAC
Regulation
(Normal Mode)
+/-15% (Max) of nominal voltage
Regulation
(Battery Mode)
+/- 5%
Voltage Waveform
Sine wave
Frequency
50Hz or 60Hz
Overload
Capability
Normal Mode
110 % ± 8 %,fault after 3 minutes;130% ± 8 %,fault after 10 cycles minimum
Boost/Buck Mode
80%+ 8 %/-4%
;
overload alarming after 25minutes
,
fault after 30minutes
Battery Mode
110 % ± 8 %,fault after 30 seconds
;
120 % ± 8 %,fault after 5 cycles minimum
Transfer
Time
Typical
2-7 ms typical, 10ms max.
Efficiency
Normal Mode
> 95% (Rated full load, battery full charged)
Boost/Buck Mode
> 90% (Rated full load, battery full charged)
Battery Mode
> 80% (Rated full load, battery full charged)
Battery &
Charger
Configuration
12V
,
7Ah(2)
12V
,
9Ah(2)
Type
Seals, maintenance-free, valve-regulated, lead acid
Recharge Time
<6 hours to 90%
<8 hours to 90%
Backup Time
100% SPS load
4’00’’
3’00’’
80% SPS load
5’30’’
4’30’’
50% SPS load
11’00’’
10’00’’
100W SPS load
35’00’’
40’00’’
Status
Indicators
Line mode
The 5st Green Led Lighting.
Battery mode
The 5st Green Led blinking every 10s.
Load/Battery Level
Load level in Line mode
:
≥
75%:LED1~LED4 lighting;
≥
50%:LED2~LED4 lighting;
≥
25%:LED3~LED4 lighting;
≥
00%:LED4 lighting
Battery level in Battery mode
:
≥
12.5V / BAT:LED1~LED4 lighting;
≥
11.5V / BAT:LED2~LED4 lighting;
≥
11.0V / BAT:LED3~LED4 lighting;
≥
10.5V / BAT:LED4 lighting
NOTE:
The numbers of LEDs please refer to Figure 2.