11: Autonomy limitation setting
Interface
Setting
Parameter 3:
Set up backup time on battery mode for
general outlets.
0-999:
setting the backup time in minutes from 0-999 for
general outlets on battery mode.
0:
When setting as
“
0
”
, the backup time will be only 10
seconds.
DIS:
Disable the autonomy limitation and the backup time will
depend on battery capacity. (Standard)
12: Battery total AH setting
Interface
Setting
Parameter 3:
Set up the battery total AH of the UPS.
7-999:
setting the battery total capacity from 7-999 in AH.
Please set the correct battery total capacity if external
battery bank is connected.
13: Charger maximum current setting
Interface
Setting
Parameter 3:
Set up the charger maximum current.
1/2/4/6/8:
setting the charger maximum current
1/2/4/6/8* in Ampere. (Default: 8A)
*Note: This setting is only available for super charger.
14: Charger Boost voltage setting
Interface
Setting
Parameter 3:
Set up the charger boost voltage.
2.25-2.40:
setting the charger boost voltage from 2.25
V/cell to 2.40V/cell. (Default: 2.36V/cell)
15: Charger Float voltage setting
Interface
Setting
Parameter 3:
Set up the charger float voltage.
2.20-2.33:
setting the charger float voltage from 2.20
V/cell to 2.33V/cell. (Default: 2.28V/cell)
00: Exit setting
Содержание VFI 1000 LCD
Страница 2: ......
Страница 24: ......
Страница 46: ......
Страница 48: ......
Страница 70: ......
Страница 92: ......
Страница 116: ......
Страница 137: ...20 IT ...
Страница 138: ......
Страница 140: ......
Страница 161: ......
Страница 163: ......
Страница 165: ......
Страница 185: ......
Страница 202: ...17 AR ...