ENGLISH 

VIII.

 

Technical Specification 

MODEL 

1000 

2000 

3000 

POWER 

1000 VA / 800 W 

2000 VA / 1600 W 

3000 VA / 2400 W 

INPUT 

Voltag

Range 

Low 

Line 

Transfer 

110-160VAC±5%  

Depending on the load level (gradually from 100% to 0%) 

Low 

Line 

Comeback 

125-175VAC± 5 %  

Depending on the load level (gradually from 100% to 0%) 

High 

Line 

Transfer 

300 VAC ± 5 %  

High 

Line 

Comeback 

290 VAC ± 5 %  

Frequency Range 

40Hz ~ 70 Hz 

Power Factor 

> 0.99 @ nominal voltage (input voltage) 

OUTPUT 

Output voltage 

200/208/220/230/240VAC 

AC Voltage Regulation  

±1% (Batt. Mode) 

Frequency Range  

47 ~ 53 Hz or 57 ~ 63 Hz (Synchronized Range) 

Frequency  Range  (Batt. 

Mode) 

50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz 

Overload 

in 

battery 

mode 

Ambient Temp.<35

0

105%~110%: 10 min; 110%~130%: 1min; >130%:3s 

UPS transfers immediately to bypass when the utility is normal 

Current Crest Ratio 

3:1 

Harmonic Distortion 

<

 3 % THD (linear load); 

<

 6 % THD (non-linear load) 

Transfer 
Time 

AC  Mode  to 
Batt. Mode 

Zero 

Inverter 

to 

Bypass 

4 ms (Typical) 

Waveform (Batt. Mode) 

Pure Sinewave 

EFFICIENCY 

AC Mode 

88% 

89% 

90% 

Battery Mode 

83% 

87% 

88% 

BATTERY 

Battery Type 

12 V / 9 AH 

12 V / 9 AH 

12 V / 9 AH 

Numbers 

Recharge Time 

4 hours recover to 90% Power (Typical) 

Charging Current  

1.0 A (max.) 

Charging Voltage  

27.4 VDC ± 1% 

54.7 VDC ±1% 

82.1 VDC ±1% 

PHYSICAL 

Dimension,  D  x  W  x  H 
(mm) 

282 X 145 X 220 

397 X 145 X 220 

421 X 190 X 318 

Net Weight (kgs) 

9.8 

17 

27.6 

ENVIRONMENT 

Operation Humidity 

20-90 % RH @ 0- 35 degC (non-condensing) 

Noise Level 

Less than 50dBA @ 1 Meter 

MANAGEMENT 

Smart RS-232 or USB 

PowerWalker ViewPower 

Optional SNMP 

Power management from SNMP manager and web browser 

Содержание VFI 1000 C LCD

Страница 1: ...des and the codes are listed in details in 3 5 section Indicates that the UPS alarm is disabled Indicates the output voltage frequency or battery voltage Vac output voltage Vdc battery voltage Hz frequency Indicates the load level by 0 25 26 50 51 75 and 76 100 Indicates overload Indicates the load or the UPS output is short circuit Indicates the UPS connects to the mains Indicates the battery is ...

Страница 2: ...he input voltage or frequency or battery voltage Vac Input voltage Vdc battery voltage Hz input frequency II Rear panel view 1 AC input 5 SNMP intelligent slot option 2 Input circuit breaker 6 Output receptacles 3 USB communication port 7 Output terminal only 3kVA unit 4 RS 232 communication port III Communication connection USB port RS 232 port Intelligent slot Apart from standard USB Port the UP...

Страница 3: ...unding every second No Battery fault Sounding every second No Out of bypass voltage range Sounding every second No Bypass frequency unstable Sounding every second No EEPROM error Sounding every second No Fault Continuously sounding Yes V Frequency Converter Mode When input frequency is within 40 Hz to 70 Hz the UPS can be set at a constant output frequency 50 Hz or 60 Hz The UPS will still charge ...

Страница 4: ...t selection in UPS setting mode down key ON Mute Select Button When the main power is normal press ON Mute and Select buttons simultaneously for 5 seconds Then UPS will enter to bypass mode This action will be ineffective when the input voltage is out of acceptable range VII UPS Setting Parameter 1 Parameter 2 Parameter 3 01 Output voltage setting 200 208 220 230 240 Value in V AC 02 Frequency Con...

Страница 5: ... 0 C 105 110 10 min 110 130 1min 130 3s UPS transfers immediately to bypass when the utility is normal Current Crest Ratio 3 1 Harmonic Distortion 3 THD linear load 6 THD non linear load Transfer Time AC Mode to Batt Mode Zero Inverter to Bypass 4 ms Typical Waveform Batt Mode Pure Sinewave EFFICIENCY AC Mode 88 89 90 Battery Mode 83 87 88 BATTERY Battery Type 12 V 9 AH 12 V 9 AH 12 V 9 AH Numbers...