background image

 

 

 

ENGLISH 

disable or enable the alarm system. But it’s not applied to the situations when warnings 
or errors occur.  

 

Press this button to display previous selection in UPS setting mode (up key) 

 

Press and hold ON/Mute button for 5 seconds to enter UPS self-testing while in AC 
mode, ECO mode, or converter mode. 

OFF/Enter Button  

 

Press and hold this button at least 2 seconds to turn off the UPS. UPS will be in standby 
mode under power normal or transfer to Bypass mode if the Bypass enable setting by 
pressing this button.  

 

Press this button to confirm selection in UPS setting mode.  

Select Button  

 

Press this button to change the LCD message for input voltage, input frequency, battery 
voltage, output voltage and output frequency. It will return back to default display when 
pausing for 10 seconds.  

 

Press and hold this button for 5 seconds to enter UPS setting mode when UPS is in 
standby mode or bypass mode.  

 

Press this button to display next selection in UPS setting mode. (down key) 

ON/Mute + Select Button 

 

When the main power is normal, press ON/Mute and Select buttons simultaneously for 5 
seconds. Then UPS will enter to bypass mode. This action will be ineffective when the 
input voltage is out of acceptable range.  

 

VII.

 

UPS Setting 

Parameter 1 

Parameter 2 

Parameter 3 

01 

Output  voltage 

setting 

 

200/208/220 

/230/240 

Value in V AC 

02 

Frequency 
Converter Mode 

CF 

Converter Mode 

ENA/dIS 

Enable or Disable (default) 

03 

Output 
frequency 
setting 

CF 

Converter  Mode  setting  (if 
enabled)  

50 / 60 

Value in Hz 

BAT 

Battery Mode setting 

50 / 60 

Value in Hz 

04 

ECO Mode 

 

ENA/dIS 

Enable or Disable (default) 

05 

ECO 

voltage 

range setting 

HLS 

Upper Limit for Input Voltage 

Nominal  
+7V to +24V 

Value in V AC 

LLS 

Bottom  Limit  for  Input 
Voltage 

Nominal  
-7V to -24V 

Value in V AC 

06 

Bypass 

 

ENA/diS 

Enable or Disable (default) bypass 
mode 

07 

Bypass 

Input 

Voltage setting 

HLS 

Upper Limit for Input Voltage 

230-264 

Value in V AC 

LLS 

Bottom  Limit  for  Input 
Voltage 

170-220 

Value in V AC 

08 

Autonomy 
Limitation 
setting 

 

0-999 

Backup  time  limit  in  minutes.  0 
actually  means  10s  and  999 
means disabled 

00 

Exit setting 

Содержание VFI 1000 C LCD

Страница 1: ...des and the codes are listed in details in 3 5 section Indicates that the UPS alarm is disabled Indicates the output voltage frequency or battery voltage Vac output voltage Vdc battery voltage Hz frequency Indicates the load level by 0 25 26 50 51 75 and 76 100 Indicates overload Indicates the load or the UPS output is short circuit Indicates the UPS connects to the mains Indicates the battery is ...

Страница 2: ...he input voltage or frequency or battery voltage Vac Input voltage Vdc battery voltage Hz input frequency II Rear panel view 1 AC input 5 SNMP intelligent slot option 2 Input circuit breaker 6 Output receptacles 3 USB communication port 7 Output terminal only 3kVA unit 4 RS 232 communication port III Communication connection USB port RS 232 port Intelligent slot Apart from standard USB Port the UP...

Страница 3: ...unding every second No Battery fault Sounding every second No Out of bypass voltage range Sounding every second No Bypass frequency unstable Sounding every second No EEPROM error Sounding every second No Fault Continuously sounding Yes V Frequency Converter Mode When input frequency is within 40 Hz to 70 Hz the UPS can be set at a constant output frequency 50 Hz or 60 Hz The UPS will still charge ...

Страница 4: ...t selection in UPS setting mode down key ON Mute Select Button When the main power is normal press ON Mute and Select buttons simultaneously for 5 seconds Then UPS will enter to bypass mode This action will be ineffective when the input voltage is out of acceptable range VII UPS Setting Parameter 1 Parameter 2 Parameter 3 01 Output voltage setting 200 208 220 230 240 Value in V AC 02 Frequency Con...

Страница 5: ... 0 C 105 110 10 min 110 130 1min 130 3s UPS transfers immediately to bypass when the utility is normal Current Crest Ratio 3 1 Harmonic Distortion 3 THD linear load 6 THD non linear load Transfer Time AC Mode to Batt Mode Zero Inverter to Bypass 4 ms Typical Waveform Batt Mode Pure Sinewave EFFICIENCY AC Mode 88 89 90 Battery Mode 83 87 88 BATTERY Battery Type 12 V 9 AH 12 V 9 AH 12 V 9 AH Numbers...

Отзывы: