IT
Parameter 2:
Low voltage point in ECO mode. The setting range
is from -5% to -10% of the nominal voltage.
Parameter 3:
High voltage point in ECO mode. The setting range
is from +5% to +10% of the nominal voltage.
07: Frequency range for ECO mode
Interface
Setting
Parameter 2:
Set low voltage point for ECO mode.
50 Hz system: Setting range is from 46.0Hz to 48.0Hz.
60 Hz system: Setting range is from 56.0Hz to 58.0Hz.
The default value is 48.0Hz/58.0Hz.
Parameter 3:
Set high voltage point for ECO mode.
50 Hz: Setting range is from 52.0Hz to 54.0 Hz.
60 Hz: Setting range is from 62.0Hz to 64.0Hz.
The default value is 52.0Hz/62.0Hz.
08: Bypass mode setting
Interface
Setting
Parameter 2:
OPN
: Bypass allowed. When selected, UPS will run at Bypass
mode depending on bypass enabled/disabled setting.
FBD
: Bypass not allowed. When selected, it’s not allowed for
running in Bypass mode under any situations.
Parameter 3:
ENA
: Bypass enabled. When selected, Bypass mode is activated.
DIS
: Bypass disabled. When selected, automatic bypass is
acceptable, but manual bypass is not allowed. Manual bypass
means users manually operate UPS for Bypass mode. For
example, pressing OFF button in AC mode to turn into Bypass
mode.
09: Maximum battery discharge time setting
Interface
Setting
Parameter 3:
000~999:
Set the maximum discharge time from 0 min to 999
min. UPS will shut down to protect battery if the discharge time
arrives before the battery is under voltage. The default value is
990 min.
DIS:
Disable battery discharge protection and backup time will
depend on battery capacity.
10: Reserved
Interface
Setting
Reserve for future options.
11: Reserved