IT
6. Specifications
MODEL
10000
10000L
15000
15000L
20000
20000L
30000
30000L
CAPACITY*
10000VA / 9000W
15000VA / 13500W
20000VA / 18000W
30000VA / 27000W
INPUT
Voltage
Range
Low Line Loss
110 VAC(Ph-N) ± 3 % at 50% Load
176 VAC(Ph-N) ± 3 % at 100% Load
Low Line Comeback
Low Line Loss V 10V
High Line Loss
300 VAC(L-N) ± 3 % at 50% Load
276 VAC(L-N) ± 3 % at 100% Load
High Line Comeback
High Line Loss Voltage - 10V
Frequency Range
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
Phase
Three phase with Neutral
Power Factor
≧
0.99 at 100% Load
OUTPUT
Phase
Three Phase with Neutral
Output voltage
208/220/230/240VAC(Ph-N)
AC Voltage Regulation
± 1%
Frequency Range
(Synchronized Range)
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
Frequency Range (Batt. Mode)
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
Overload
AC mode
100%~110%: 10min
110%~130%: 1min
>130% : 1sec
Battery mode
100%~110%: 30sec
110%~130%: 10sec
>130% : 1sec
Current Crest Ratio
3:1 max
Harmonic Distortion
≦
2 % @ 100% Linear Load;
≦
5 % @ 100% Non-linear Load
Transfer
Time
Line
Battery
0 ms
Inverter
Bypass
0 ms (When phase lock fails, <4ms interruption occurs from inverter to bypass)
Inverter
ECO
<10 ms
EFFICIENCY
AC mode
> 89%
>89%
>89%
>90%
Battery Mode
> 86%
>88%
>87%
>89%
BATTERY
Standard
Model
Type
12 V / 9 Ah
12 V / 9 Ah
12 V / 9 Ah
12 V / 9 Ah
Numbers
20(18-20 adjustable)
2 x 20(18-20 adjustable) 2 x 20(18-20 adjustable) 3 x 20(18-20 adjustable)
Recharge Time
9 hours recover to 90% capacity
Charging Current
1.0 A ± 10% (max.)
2.0 A ± 10% (max.)
2.0 A ± 10% (max.)
4.0 A ± 10% (max.)
Charging Voltage
273 VDC ± 1%
Long-run
Model
Type
Depending on applications
Numbers
18 - 20
Charging Current
4.0 A ± 10% (max.)
4.0 A ± 10% (max.)
4.0 A ± 10% (max.)
12.0 A ± 10% (max.)
Charging Voltage
273 VDC ± 1%
PHYSICAL
Outline
Dimension, D X W X H
mm
815X250
X826
592X250
X826
815X250
X826
592X250
X826
815X250
X826
592X250
X826
815 X 300 X
1000
815X250
X 826
Net Weight (kgs)
109
38
164
40
164
40
233.5
64
Packaging
Dimension, D X W X H
mm
920X380
X1025
700X385
X1071
920X380
X1025
700X385
X1071
920X380
X1025
700X385
X1071
920 X 430 X
1205
920X380
X 1025
Net Weight (kgs)
127
45
182
47
182
47
250.5
90
ENVIRONMENT
Operation Temperature
0 ~ 40°C (the battery life will down when > 25°C)
Operation Humidity
<95 % and non-condensing
Operation Altitude**
<1000m
Acoustic Noise Level
Less than 60dB @
1 Meter
Less than 65dB @ 1 Meter
MANAGEMENT
Smart RS-232 or USB
Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix, and MAC
Optional SNMP
Power management from SNMP manager and web browser
* Derate capacity to 90% when the output voltage is adjusted to 208VAC.
**If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m.
***Product specifications are subject to change without further notice.
Содержание 10000
Страница 2: ......