4
It is worth taking care to install the system correctly and to have it
maintained correctly by your local dealer.
1.1.25. SAVE THESE INSTRUCTIONS. This manual contains important
instructions that should be followed during installation and maintenance
of the UPS and batteries.
1.1.26. The UPS is intended for installation in a controlled environment.
1.1.27. CAUTION: A disconnect switch must be provided by others for the AC
output circuit. To reduce the risk of fire connect only to a circuit provided
with branch circuit over-current protection for 30 amperes for 6 kVA and
40 amperes for 8 kVA (See below for 10 kVA details) rating in accordance
with the National Electric Code, ANSI/NFPA 70.
10 kVA tower
Output No.
Output rating
Ratings of output branch circuit
over-current protection
No.1 (L21-N21)
5 kVA, 120 V
45
No.2 (L22-N22)
5 kVA, 120 V
45
No.3 (L23-N22)
10 kVA, 208 V
50
No.4 (L21-N22)
10 kVA, 240 V
45
1.1.28. CAUTION: To reduce the risk of fire connect the UPS only to a circuit
provided with branch circuit over-current protection for 40 amperes for 6
kVA and 70 amperes for 8/10 kVA rating in accordance with the National
Electric Code, ANSI/NFPA 70.
1.1.29. Install the UPS so that it is not likely to be contacted by people.
1.1.30. The maximum ambient operating temperature is 40
C or equivalent.
1.1.31. Units are considered acceptable for use in a maximum ambient 40°C
1.1.32. CAUTION - RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN
INCORRECT TYPE. DISPOSE OF USED BATTERIES ACCORDING TO
THE INSTRUCTIONS.
1.1.33. CAUTION - Do not dispose of batteries in a fire. The batteries may
explode.
1.1.34. CAUTION
– Do not open or mutilate batteries. Released electrolyte is
harmful to the skin and eyes. It may be toxic.
1.1.35. CAUTION
– A battery can present a risk of electrical shock and high short
circuit current. The following precautions should be observed when
working on batteries:
Содержание 10000
Страница 1: ...Parallel Redundancy On Line UPS User Manual 4 5 6 8 10 15 and 20 kVA ...
Страница 14: ...13 2 3 2 Rear Panel Also available for Rack ...
Страница 22: ...21 ...
Страница 27: ...26 J frequency of Utility Input K frequency of Bypass Input L UPS output voltage M UPS output frequency N UPS ...
Страница 29: ...28 buzzer Off ...
Страница 32: ...31 The UPS is operating in CVCF 50 Hz mode ...
Страница 44: ...43 1 2 3 6 6 Interface Card Installation ...
Страница 46: ...45 ...
Страница 52: ...51 192321132115000 ...