19
N21
L23
240Vac
120Vac
120Vac
208Vac
L21
6KVA (Max)
6KVA (Max)
3KVA (Max)
3KVA (Max)
N22 L22
●
L11-N1
、
B-N1:
the terminal for Bypass Input to provide the power source when
the UPS is working under bypass mode
●
L12-N1
、
R-S-T-N1
: the terminal for Utility Input to provide the power source
when the UPS is working under Utility mode
●
G1:
the terminal for UPS Input Ground
●
L21
、
L23
、
N21
、
L22
、
N22:
the terminals for UPS Output
●
G2:
the terminal for UPS Output Ground
Remarks:
1. The maximum current for each terminal is 30 Arms for 6 kVA, 50 Arms for 10
kVA, 100 Arms for 20 kVA.
2. If the UPS is a DIM (Dual Input) type whose Utility and Bypass Sources are
the same, L11 and L12 must be shorted for the 1-phase input model, and B
and R must be shorted for the 3-phase input model.
3. If the UPS is a SIM (Single Input) type, only AC source can be supplied to
the UPS from the L12-N1 terminal for the 1-phase input model and from the
R-S-T-N1 terminal for the 3-phase input model.
4. When the isolation transformer is not installed into the tower-type UPS the
UPS output terminals will be L22-N22.
5. Use No. 6 AWG, 75
C minimum copper wire and 23 lb-in Torque force when
connecting to terminal block
6. When the isolation transformer
is
installed into the tower-type UPS:
a. For 100/110/115/120 VAC systems you may connect as shown below.
b. For 200/100 VAC, 220/110 VAC, 230/115 VAC, 240/120 VAC, or
240/208/120 VAC systems you may connect as shown below.
N22
L22
N21
110Vac
L23
L21
6KVA (Max)
Содержание 10000
Страница 1: ...Parallel Redundancy On Line UPS User Manual 4 5 6 8 10 15 and 20 kVA ...
Страница 14: ...13 2 3 2 Rear Panel Also available for Rack ...
Страница 22: ...21 ...
Страница 27: ...26 J frequency of Utility Input K frequency of Bypass Input L UPS output voltage M UPS output frequency N UPS ...
Страница 29: ...28 buzzer Off ...
Страница 32: ...31 The UPS is operating in CVCF 50 Hz mode ...
Страница 44: ...43 1 2 3 6 6 Interface Card Installation ...
Страница 46: ...45 ...
Страница 52: ...51 192321132115000 ...