23
3.5.1.5. The UPS is in Bypass Mode now. It will proceed to self-test
automatically. If no abnormal message appears then the pre-
startup of the UPS was successful and the charger starts to
charge the batteries.
3.5.1.6. Press the UPS On Switch
for approximately three seconds.
The Buzzer sounds twice and the LCD display changes from
figure B to figure C.
C
3.5.1.7. The UPS is in self-test mode again. The LCD display will change
from figure C to figure D, and the UPS will remain in battery mode
for approximately four seconds. Then the display will change from
figure E1 to figure F if the self-test was successful.
D
“test”
E1
“OK” in self-test
E2
“Fail” in self-test