3.4.4. Battery Charging Requirements PCE for P Series
Eco P Series Installation Manual V3.0
21/10/2021
Page
of
11
37
Connected PCE Programming Requirements
Eco4833P
Shutdown DC Voltage @0.5C
48.0V
Shutdown Voltage Recommended
50.2V
Recovery / Restart Voltage
52V
Continuous Charge Voltage
57.6V
Continuous Charge Transition
Battery
is considered full after battery is absorbing less than 1% of maximum charge current after being held at
specified charge voltage for 30minutes minimum.
Float Voltage Cyclic
(Short Term Float)
(Example Solar Application)
57.6V
Float Voltage Standby
(Long Term Float)
(Example UPS Application)
54.4V to 56V
Charge Current
39A
Peukert Exponent
1.02
Shutdown SoC Recommended
20%
Calibration to 100%
Every 7 days or more frequent where possible.
(Ensures cell balancing is performed & keeps external SoC counter more accurate)
Note
These charging requirements are subject to change at anytime without notice