5. Connection and Operation

 

 

 
 
 

 
 
 
 
 
 
 

 
 

5.1 Inspection:

 

Inspect the packing carton and its contents for any damage. 

Inform  the  carrier  agency  immediately  if  you  find  any  sign  of  damage. 

Keep the packing cartons in a safe place for future use.

 

 

Note: Please ensure that the incoming feeder is isolated and secured 

to prevent it from being switched on again. 

   

5.2 Connection 

 

5.2.1 UPS Input Connection 

The current carrying capacity (ampacity) of the socket outlet, to which the 

UPS is connected, must  be  greater  than the UPS input current: over  10A 

for 

1KT-XL

 

and  2KT

  models and over 16A for 

3KT

  and 3KT-XL

 

models.

 

 

5.2.2 UPS Output Connection 

   

 The outputs of the UPS 1KT

  and 1KT-XL

 

are socket-type only. Simply plug 

the load power cord to the UPS output socket to complete the connection. 

 

UPS Model 

Number of Socket Outlets 

Output Terminal Block 

No 

2KT 

No 

2KT-XL 

6

3

Yes 

This UPS system has to be wired and installed by a qualified 
technician  and  in  accordance  with  the  applicable  safety 
regulations. 

 

When  installing  the  electrical  wiring  of  the  UPS,  please  take 
into  consideration  the  rated  current-carrying  capacity 
( ampacity ) of the incoming feeder. 

 

1KT/1KT-XL

3KT/3KT-XL

1KT,

2KT-XL,

(IEC)

No 

Содержание 1KT

Страница 1: ...USER MANUAL LCD 1 3Kva models Uninterruptible Power Supply...

Страница 2: ...ng Modes 6 1 Line Mode of Operation 6 2 Battery Mode of Operation 6 3 Bypass Mode of Operation 6 4 No Output Mode of Operation 6 5 Abnormal Mode of Operation 7 Setting the UPS Parameters 8 Troubleshoo...

Страница 3: ...near heat Do not block off the ventilation openings of the UPS cabinet 1 3 Installation Do not connect appliances or items of equipment which may overload the UPS such as laser printers to the output...

Страница 4: ...he UPS is not connected to an AC supply For complete disconnection of the UPS system first press the OFF button for more than one second then disconnect the mains power supply cable Ensure that no flu...

Страница 5: ...an present a risk of electrical shock and have high short circuit current The following precautions and any others necessary measures should be observed Remove watches rings or other metal objects Use...

Страница 6: ...should be familiar with these symbols and understand their meanings Symbol Explanation Caution Special Attention is Required Risk of Electric Shock Turning ON the UPS Turning OFF the UPS Idle or Shutd...

Страница 7: ...he inverter in its turn generates a sinusoidal AC voltage which permanently supplies the loads with uninterrupted clean and sine wave voltage Computers and peripherals are thus powered entirely by the...

Страница 8: ...OFF button the inverter turns off and if the mains power supply is normal the UPS system switches to Standby or Bypass mode The UPS output sockets will be supplied via the bypass circuit Select Button...

Страница 9: ...specified range the UPS will work in the battery mode Indicates that the input supply voltage is lower than the specified range the UPS will work in the battery mode Output Information Displays the va...

Страница 10: ...de and the warning codes of the UPS For the meaning of these codes refer to page 13 Inverter operating Information Indicates that the inverter is running Bypass operating Information Indicates that th...

Страница 11: ...eater than the UPS input current over 10A for 1KT XL and 2KT models and over 16A for 3KTand 3KT XL models 5 2 2 UPS Output Connection The outputs of the UPS1KT and 1KT XL are socket type only Simply p...

Страница 12: ...r 2KS 3K and 3KT XL models 5 2 3 Computer Connection Connect your computer to the UPS socket outlet using the above diagram 5 3 Battery Charging To fully charge the batteries of the UPS keep the UPS c...

Страница 13: ...st the UPS press the ON button of the UPS or disconnect the input mains supply 5 6 Turning Off the UPS 5 6 1 In Line Mode Press the OFF button continuously for more than one second At the beginning th...

Страница 14: ...o the external battery cabinet 3 Do not connect any load to the UPS output Connect the input power cable of the UPS to the input mains supply to operate the UPS in the utility power mode 4 Connect the...

Страница 15: ...be displayed and only the code of the existing fault will be displayed Operating mode code Operating mode code No output mode 00 Overload fault 07 Bypass mode 01 Over temperature fault 08 Line mode 02...

Страница 16: ...ER on the LCD display indicates that the inverter is in operation Note that 1 When the UPS is in the battery mode the alarm beeps once every 4 seconds To silence the alarm press the ON button for more...

Страница 17: ...at indicates the battery test mode is 04 6 3 Bypass Mode of Operation The LCD display of the UPS in the bypass mode of operation is shown in the figure below In this mode of operation information abou...

Страница 18: ...ins supply the battery the UPS output and the load are displayed The code that indicates this mode of operation is 00 Fig 6 4 No output mode of operation 6 5 Abnormal Mode of Operation This mode of op...

Страница 19: ...an one second a flickering black round dot will be shown in front of the 208V on the LCD If the Select button is again pressed continuously the flickering dot will move to the front of the 220V 230V 2...

Страница 20: ...ressing the Select button for more than one second one flicking round dot will appear in front of the 208Vac Step 2 Pressing the Select button twice again the flicking round dot will move to the front...

Страница 21: ...he dot in front of the 230Vac will stop flicking and the dot in front of the 240Vac will begin flicking This indicates that the output voltage 230Vac has been selected Step 4 After the UPS turns to ON...

Страница 22: ...hown on the LCD panel and the warning word H or L may be also displayed Input power supply voltage and or frequency is out of tolerance Check the input power supply source and inform the service repre...

Страница 23: ...backup time Contact the service representative Warning code 13 is shown on the LCD panel the alarm beeps once per second Charger or Battery faulty Contact the service representative Warning code 10 is...

Страница 24: ...eeded the batteries have to be replaced For battery replacement contact your dealer 9 2 Storage If the UPS is stored in a temperate climatic environment recharge the battery every three months by conn...

Страница 25: ...0 240 2 VAC Frequency 50 60 0 2 Hz Battery mode Waveform sinewave Note The output power of the UPS is de rated to 90 of its nominal value when the output voltage of the UPS is adjusted to 208V Batteri...

Страница 26: ...34 5 2KT XL 192X460X340 15 3KT 192X460X340 35 5 3KT XL 192X460X340 16 10 5 Safety and EMC Standards GB4943 EN62040 1 1 safety Conducted Emission GB7260 2 EN62040 2 Class B Radiated Emission GB7260 2 E...

Страница 27: ...ional accessory for AS400 communication protocol This interface provides true relay contact output to peripheral devices The following is the pin assignment and description of DB 9 connector in AS400...

Страница 28: ...e these UPS systems W Installation Procedure The following is the installation procedure for the WinPower software 1 Connect to the website http www ups software download com winpower htm 2 From the d...

Страница 29: ...Appendix 1 UPS Rear Panel The rear panel of the 1KT and 1KT XL models The rear panel of the 2KTmodel...

Страница 30: ...The rear panel of the 3KT and 3KT XL models...

Отзывы: