Willo Instruction Manual
7
Operation
Starting Up
1. Check all connections.
2. Switch the Surge Protection Device (SPD) breaker ON.
3. Switch BATT breaker ON.
4. Switch the AC input ON.
5. Confirm UPS starts up.
6. Switch output breaker ON and confirm operation of attached equipment.
Please refer to UPS manual for detailed operation of the UPS.
Switching Off
1. Power down the attached loads.
2. Open the door over Tier 3, and press and hold for 2 seconds the OFF switch on the
UPS.
3. Open the battery breakers.
4. Open the AC output breaker.
5. Open the AC input breaker.
6. The UPS should now be completely switched off, and the loads will be off.
7. Before carrying out any maintenance on the power distribution panel, ensure that the AC
supply feeding the Willo cabinet is disconnected.
Maintenance
1. Maintenance should only be carried out by competent persons and involves checking
live AC sources.
2. Check Surge Protection Device Inspection Windows are Green. If RED, it requires
replacement.
3. Check external fan activates, by placing a shorting link over the terminals of the
thermostat. It is advisable to disconnect the AC power before fitting the link (usually via
the AC Output Breaker).
4. Check the integrity of connections on both the front panel AC terminals, and the breaker
terminations.
5. Ensure battery terminations are tight and robust.
6. Check battery integrity for signs of any leaks or cracks, or any distortion to the battery
casing.
7. Check battery voltage.
8. Ensure batteries hold up by disconnecting the AC input breaker.