Willo Instruction Manual
6
AC Power Connections
1. The AC input and output power cables are fed into the Willo cabinet through the oval cut
outs in the floor of the unit at the front.
2. The AC input and output terminals are located on the door of the shelf of Tier 3. Remove
the cover to access the terminals.
3. Connect the AC input and output power cables to the appropriate terminals, marked L,
N, PE (Live, Neutral & Protective Earth). We recommend the cables are ferruled or fitted
with ring or fork crimps.
4. Other AC equipment can also be connected directly to the output terminals of the UPS if
required.
Equipment Installation
1. Note that it is not advisable to dissipate more than 200W within the cabinet as excessive
temperature build up could arise, diminishing battery life and affecting unit performance.
2. Customer equipment can be located in the middle tier, or, if taken by batteries and if
small enough, in the upper tier along with the UPS.
3. A DIN rail is provided in the top tier to mount DIN rail equipment
UPS Installation
1. Remove the battery connection terminal plate from the rear of the unit.
2. Place the UPS into the top tier of the Willo cabinet.
3. Ensure all breakers are in the OFF position.
4. Connect the IEC C13 cable (with unexposed conductors) into the UPS input.
5. Connect the IEC C14 cable (exposed conductors) into one of the UPS output
connectors.
6.
Connect the Anderson cable marked “UPS” into the battery terminal of the UPS. Ensure
a good fit.