background image

 

User Manual 

 

 

5

 

Safety 

 

WARNING! 

THIS UPS IS CLASSED AS PLUGGABLE TYPE B OR PERMANENTLY 

CONNECTED EQUIPMENT AND MUST BE INSTALLED, COMMISSIONED AND 
MAINTAINED BY A QUALIFIED ELECTRICIAN. AN APPROPIATE AND READILY 
ACCESIBLE DISCONNECT DEVICE MUST BE INCORPORATED INTO THE FIXED SUPPLY 
WIRING TO THE UPS. 

There are dangerous voltages and high temperatures inside the UPS. During installation, operation and 
maintenance please abide by local safety instructions, regulations and laws. Failure to do so may result in 
injury to personnel or damage to equipment. Safety instructions in this manual are supplementary to local 
safety instructions. Power Inspired does not accept any liability caused as a result of failure to 
follow safety instructions. Please note the following: 

Do not operate the UPS in an environment or application outside of that detailed in the user manual. 

Do not exceed rated load of UPS and ensure it operates in a dry, well ventilated location away from 
any area or situation in which there is a risk of fire, such as direct sunlight or other sources of heat. 

Under no circumstances open the UPS as there are no user serviceable parts.  There are high 
capacity batteries inside and other electronics that can cause electric shock. If the UPS requires 
internal maintenance or battery replacement, contact Power Inspired.

 

In pluggable type B applications the UPS must be switched off and isolated prior to removal of the 
AC mains input plug from the mains supply socket, as detailed on the warning label fitted on the UPS. 

The UPS mains input cable must be connected to an earthed mains supply for operator safety and 
EMC compliance. 

If the UPS emits smoke, turn off immediately the input circuit breaker at the back of the unit and, if 
fitted, the battery circuit breaker, and contact Power Inspired.

 

EMC 

 

WARNING! 

This is a product for commercial and industrial applications in the second 

environment. 

This is a category C2 UPS product. In a residential environment, this product may cause 
radio interference, in which case the user may be required to take additional measures. (As 
stated in: EN62040-2:2006). 

Warning symbols 

The safety symbols used in this manual are shown in table below. They alert you to important safety 
information that you need to be aware of when installing, operating and maintaining the UPS. 

Safety Symbol 

 

I

ndication

 

 

Attention 

 

 

 

Static discharge sensitive 

 

Electric shock 

 

 

Caution: 

A caution describes a situation in which there is a risk of damage to equipment. 

 

VFI-KT Series User Manual

Содержание VFI10KT

Страница 1: ...POWER INSPIRED LTD Units 5 7 High Point Riding Road Brackley NN13 7BH UK info powerinspired com www powerinspired com 44 0 1280 811180 MAN VFI KT REV2 User Manual VFI KT Series UPS VFI6KT VFI10KT...

Страница 2: ...nt Notes Please contact Power Inspired if you intend to use the UPS in an application that has an impact on human life such as Life Support Equipment Critical escape routes such as elevators or re doo...

Страница 3: ...11 Wiring units in parallel 12 Operation 14 Working modes 14 On Line mode 14 Bypass mode 14 Battery mode 14 ECO mode 14 Before switch on 15 Switching on the UPS 15 Switching off the UPS 16 Swapping ou...

Страница 4: ...rd advanced monitoring and control 25 Relay card advanced monitoring and control 25 Appendix 2 Parallel board signals 27 LBS Load Bus Synchronisation 27 Dry contact relay signals 27 Appendix 3 Speci c...

Страница 5: ...are high capacity batteries inside and other electronics that can cause electric shock If the UPS requires internal maintenance or battery replacement contact Power Inspired In pluggable type B appli...

Страница 6: ...reliable AC backup power to various types of equipment for example computer centres network management centres analytical equipment and telecommunication systems Product range The VFI KT series is av...

Страница 7: ...nversion and a wide input voltage range ensure continuous output for areas with poor power supply regulation DSP technology for digital control ensures high reliability circuit protection and self dia...

Страница 8: ...the equipment If the UPS is to be supplied from a local transformer ensure the transformer kVA rating is at least 50 greater than the UPS output kVA rating Use circuit breakers and cables with the co...

Страница 9: ...CCB Caution When installing external battery packs do not use an MCB breaker in the battery line as this type of breaker is not rated for the d c battery voltage Instead use an MCCB breaker that is ra...

Страница 10: ...Rear panel layout Fan Removable Bypass Module On Off Switch Bypass Switch Cover Handle Outlet Gland Plate EPO Switch RS232 Port USB Port SNMP Relay Card Slot Parallel Card Slot VFI KT Series User Manu...

Страница 11: ...r order b Measure the battery voltage The voltage should be approximately 192 Vd c for 16 batteries 216 Vd c for 18 batteries and 240 Vd c for 20 batteries 192Vdc 16 batteries is default 2 On the rear...

Страница 12: ...bypass for the parallel system it must be wired as an external item WARNING BEFORE ATTEMPTING TO WIRE THE UNITS ENSURE ALL BREAKERS ARE IN THE OFF POSITION To connect two or more units in parallel 1...

Страница 13: ...connection You can control and monitor all units using the RS232 port on one UPS To do this connect the pink RS485 socket of one unit to the green RS485 socket of the next unit and so on until all un...

Страница 14: ...st be repaired The UPS is turned off In bypass mode the Inverter LED is off and the Bypass LED is on Battery mode In battery mode the load is supplied from the battery via the inverter the UPS beeps e...

Страница 15: ...r installation has an external battery switch on the battery breaker 3 Switch on the input breaker 4 On the rear panel switch on the unit main breaker Note If switching on into a transformer load ensu...

Страница 16: ...e load 1 On the front panel press OFF to switch the unit to bypass mode 2 When prompted by the LCD press Ent to con rm your action The Bypass LED turns on and the Inverter LED turns off 3 Access the r...

Страница 17: ...aded Battery On when the power is supplied from the battery The LED ashes if the battery is low or disconnected Mains On when mains in present and within limits The LED ashes if the mains is outside i...

Страница 18: ...can be traversed using the buttons Use ENT to and select or ESC to return to the previous menu Note The values shown below are examples only The values in your system are likely to be different Figure...

Страница 19: ...s and pressing and ENT Change to ECO mode by navigating to MODE and cycling through the options until ECO is displayed Con rm by pressing ENT SETTING Mode ECO Batt Num 16 Batt cap 9Ah The next screen...

Страница 20: ...screen allows you to perform a series of battery tests SETTING BatTest Off The options are Off Test1 Test2 and Test3 The next screen allows you to con gure the unit for parallel operation SETTING Para...

Страница 21: ...tin Starting CurState ECO UPS running in ECO power saving mode CurState EPO Emergency Power OFF mode CurState M Byp UPS in maintenance bypass mode CurState Fault UPS fault Battery Charging Battery oat...

Страница 22: ...12 hours every 3 months if it has not been used If the ambient temperature is higher than 25 C charge the battery every 2 months Maintain external batteries at least once a year If the backup time ha...

Страница 23: ...y mode 6 Buzzer beeps twice every second LCD displays output overload UPS overload Reduce the load on the UPS 7 Fault indicator on LCD displays battery fault a Battery circuit breaker off or poor conn...

Страница 24: ...3 TDX 3 RX 2 GND 5 GND 5 RS232 communication data format Parameter Value Baud rate 2400 bps Byte length 8bit End bit 1bit Parity check Null Contact closure basic monitoring and control The VFI KT uni...

Страница 25: ...d monitoring and control functionality via a set of dry contacts and a single opto coupled input Connections Pin no Description n Contact status Additional fault information 1 Mains out of limits clos...

Страница 26: ...orward input voltage 30 Vd c max 5 to 12 Vd c typical Forward current 25 mA max 16 mA typical Pulse forward current IFP 1 A 100 s pulse 100 pps To connect to the relay card 1 On the rear of the UPS un...

Страница 27: ...s a 12 V 100 mA isolated supply 2 GND Common return 0 V for the 12 V supply and relays This is not connected to the chassis 3 Remote ON Connect to 12V to turn on the UPS pulse contact 4 Remote OFF Con...

Страница 28: ...frequency range 1 2 4 5 10 THDI 3 100 linear load input THDV 1 5 100 non linear load input THDV 1 Battery Number of 12 V batteries 16 18 or 20 batteries in series centre tapped Battery type VRLA Char...

Страница 29: ...n normal mode and battery mode 0 ms Between inverter and bypass 0 ms unlock 15 ms 50 Hz 13 33 ms 60 Hz Parallel operation Parallel equal current 1 1 8 N 1 10 Safety and EMC Safety IEC62040 1 GB4943 Is...

Страница 30: ...0KT 64 kg Audible noise 55dB 1m Colour Black Display LCD and LED Ingress protection IP20 Appendix 4 Optional equipment The following items are available as options for the UPS External Battery PAck Dr...

Страница 31: ...4 5 6 7 C D E F Charging 2 3 6 7 A B C E F P battery boost charging 1 3 5 7 9 B D F N battery boost charging 8 9 A B C D E F Battery self testing 4 5 6 7 C D E F 00 shutdown 01 soft start 10 no outpu...

Страница 32: ...7 9 B D F Discharge SCR fault 8 9 A B C D E F Charge SCR fault 4 5 6 7 C D E F Fan fault 2 3 6 7 A B C E F Fan supply fault 1 3 5 7 9 B D F BUS over voltage 8 9 A B C D E F BUS lower voltage 4 5 6 7...

Страница 33: ...unication fault 1 3 5 7 9 B D F Parallel current not equal 8 9 A B C D E F Bypass phase wrong 4 5 6 7 C D E F Sync fault 2 3 6 7 A B C E F Bypass over track 1 3 5 7 9 B D F Bypass over protect 8 9 A B...

Страница 34: ...POWER INSPIRED LTD Units 5 7 High Point Riding Road Brackley NN13 7BH UK info powerinspired com www powerinspired com 44 0 1280 811180 MAN VFI KT REV2...

Отзывы: