19
VFI-KT Series User Manual
Status menu items
These menu items provide UPS system information only.
STATUS
Code: 5
Fault: 0 0 0 0
Model: 10KVA
STATUS
Version
V03B05D002
Setting menu items
These menu items allow you to change the UPS settings.
SETTING
Mode: NOR
Batt Num: 16
Batt cap: 9Ah
You can change the setting by navigating to the required section using the
buttons and pressing
◄ and ►
ENT.
Change to ECO mode by navigating to MODE, and cycling through the options until ECO is displayed.
Confirm by pressing ENT:
SETTING
Mode: ECO
Batt Num: 16
Batt cap: 9Ah
The next screen allows you to adjust the output voltage and frequency. The options are 220, 230 and
240V; 50 or 60Hz:
SETTING
V-Level: 230V
F-Levle: 50Hz
The next screen allows you to adjust the input voltage trip points at which the UPS will revert to battery
operation:
SETTING
V-upper: 15%
V-lower: 45%
The upper voltage options are 10, 15 or 20%.
The lower voltage options are 20, 30 or 45%